Esc
user@example.com
View Profile
advanced Power Systems

Protection Coordination (IEC Inverse-Time)

Plot two IEC 60255 inverse-time overcurrent relays on the same time-current diagram, slide the fault current cursor, and watch the grading margin go green or red. The minimum workflow for any feeder protection setting calculation.

1001k10k10ms100ms1s10s100sCurrent (A) — log scaleOperating time (s) — log
✓ Discrimination OK@ 3000 A
R1 (downstream feeder)0.252 s
R2 (upstream incomer)0.681 s
Margin0.429 s(need ≥ 0.30 s)
R1 (downstream feeder)
R2 (upstream incomer)
// tutorial Step 1 / 5
  1. Both relays are 'Standard Inverse' by default with R1 (downstream) faster than R2 (upstream). Slide the fault-current bar across the range and watch the grading margin readout. With 0.3 s grading required (the typical UK distribution value), there's a wide range over which discrimination holds.

    Show hint

    Standard Inverse is the IEC default. North American IEEE C37.112 'Moderately Inverse' is a different equation — don't mix the two on a single feeder.