Harmonic Analysis & G5/5 Compliance
Synthesise a distorted waveform from individual harmonic components, run an FFT, and check the spectrum against ENA EREC G5/5 voltage planning limits — the standard a UK harmonic distortion study has to demonstrate compliance with.
preset:
Synthesised waveform (1 cycle, peak = 1.00 pu)
Harmonic spectrum (% of fundamental, h2–h25). Orange dashes = G5/5 EHV limits.
THDv0.00%
G5/5 EHV limit: 3% — within limit
Harmonic content (% of fundamental)
h1
100.0%
h3
0.0%≤2%
h5
0.0%≤2%
h7
0.0%≤2%
h9
0.0%≤1%
h11
0.0%≤1.5%
h13
0.0%≤1.5%
Limits shown are ENA G5/5 EHV planning levels (UK). LV / MV systems have higher allowances.
// tutorial Step 1 / 5
-
Start with the 'Pure 50 Hz sinusoid' preset. The waveform is clean, the spectrum is empty above the fundamental, and THD = 0%. This is the goal of every PCC: deliver close-to-sinusoidal voltage to other connected customers.
Show hint
PCC = Point of Common Coupling. The harmonic limits in G5/5 apply at the PCC, not deep inside the customer's installation.
Lesson complete! Well done.