Power Systems Fundamentals
eee-roadmap.muhammadhazimiyusri.uk/roadmaps/power-system-fundamentals/
Power Network Basics
Busbars, Nodes, and Branches
Foundation concepts for understanding power system structure. Covers the building blocks of power networks: nodes as connection points, branches as circuit elements, and busbars as central distribution points.
- Identify nodes, branches, and loops in power network diagrams
- Apply Kirchhoff's laws to power circuits
- Convert circuit diagrams to graph representations
Common connection point where circuit elements meet, characterized by voltage phasor.
In power systems, each node has:
- Voltage magnitude
- Voltage angle
Circuit element connecting two nodes with impedance:
Examples: transmission lines, transformers, cables.
Non-impedant conductive bar serving as central power distribution point in substations.
Image: Wikimedia Commons, Public Domain
KCL (Current Law): Sum of currents entering a node equals sum leaving.
KVL (Voltage Law): Sum of voltages around any closed loop equals zero.
- MIT OCW 6.061 - Electric Power Systems https://ocw.mit.edu/courses/6-061-introduction-to-electric-power-systems-spring-2011/
- NPTEL Power System Engineering https://nptel.ac.in/courses/108105104
Radial vs Ring vs Mesh Networks
Power distribution network configurations and their trade-offs. Understanding when to use radial (simple/cheap), ring (reliable), or mesh (redundant) topologies for different applications.
- Classify network topologies from single-line diagrams
- Evaluate trade-offs between reliability, cost, and complexity
- Select appropriate topology for different applications
Tree-shaped network with single path from source to consumer.
Pros: Simple, lowest cost, easy protection Cons: No redundancy - single fault causes outage Use: Rural areas, residential distribution
Closed loop providing two alternative paths.
Can be operated as:
- Open ring: One point normally open (like two radials)
- Closed ring: Full loop energized (better reliability)
Use: Urban distribution, commercial areas
Multiple interconnections creating redundant paths.
Pros: Highest reliability, load sharing Cons: Complex protection, highest cost Use: Transmission networks, critical industrial loads
- Practical Engineering - How the Power Grid Works https://practical.engineering/
- Electricity Grid Schematic (Wikimedia) https://commons.wikimedia.org/wiki/File:Electricity_Grid_Schematic_English.svg
Single Line Diagrams
Reading and interpreting single-line diagrams (SLDs), the standard representation for three-phase power systems. Covers symbols, conventions, and information typically shown.
- Interpret single-line diagrams and identify all components
- Understand standard electrical symbols (IEEE/IEC)
- Trace power flow paths through systems
Simplified representation showing three-phase system as single line.
Why simplify? Three phases are balanced in normal operation, so one line represents all three.
Image: Wikimedia Commons, CC BY-SA 3.0
Standard approach:
- Start at top (highest voltage)
- Work down to lowest voltage
- Left-to-right for same voltage level
| Symbol | Component |
|---|---|
| Circle with ~ | Generator |
| Two coils | Transformer |
| Square with X | Circuit breaker |
| Heavy horizontal line | Busbar |
- Learn to Interpret SLDs - EEP https://electrical-engineering-portal.com/learn-to-interpret-single-line-diagram
- IEEE/IEC Electrical Symbols (Wikimedia) https://commons.wikimedia.org/wiki/Category:DIN_circuit_symbols
Power Flow Fundamentals
Active Power (P) and Reactive Power (Q)
Understanding the two components of AC power: real power that does useful work, and reactive power that maintains magnetic fields. Essential for power system analysis and equipment sizing.
- Calculate P, Q, and S for single and three-phase systems
- Explain physical significance of reactive power
- Construct and interpret power triangles
Real power doing useful work (motors, heating, lighting).
Units: Watts (W, kW, MW)
For three-phase:
Power that oscillates between source and load, maintaining magnetic/electric fields.
Units: Volt-Amperes Reactive (VAR, kVAR, MVAR)
- Inductors (motors, transformers): Consume Q (lagging)
- Capacitors: Supply Q (leading)
Vector sum of P and Q - total power the system must deliver.
Units: Volt-Amperes (VA, kVA, MVA)
Graphical representation relating P, Q, and S:
Image: Wikimedia Commons, CC BY-SA 3.0
- Horizontal: Active power P
- Vertical: Reactive power Q
- Hypotenuse: Apparent power S
- Angle φ: Power factor angle
- The Engineering Mindset - AC Power https://theengineeringmindset.com/electrical/
- Khan Academy - AC Circuit Analysis https://www.khanacademy.org/science/physics/circuits-topic
Power Factor
The ratio of real to apparent power, indicating how effectively electrical power is being used. Critical for efficiency, billing, and equipment sizing.
- Calculate power factor from circuit measurements
- Determine if power factor is leading or lagging
- Design power factor correction using capacitors
Ratio of real power to apparent power:
- PF = 1.0 (unity): Pure resistive, V and I in phase
- PF = 0: Pure reactive, no real power transferred
- Typical industrial: 0.7 - 0.9 lagging
Describes current relative to voltage:
- Lagging PF: Current lags voltage (inductive loads - motors)
- Leading PF: Current leads voltage (capacitive loads)
Memory aid: ELI the ICE man
- ELI: Voltage (E) leads Current (I) in Inductors (L)
- ICE: Current (I) leads Voltage (E) in Capacitors (C)
Adding capacitors to cancel inductive reactive power:
Where:
- = original PF angle
- = target PF angle
Target: PF > 0.95 to avoid utility penalties
- Power Factor Explained - Engineering Mindset https://theengineeringmindset.com/electrical/
- Power Factor Diagram (Wikimedia) https://commons.wikimedia.org/wiki/Special:FilePath/Power_Factor_General_Case.svg
Voltage Levels and Transformation
Why power systems use different voltage levels and how transformers enable efficient power transfer. Understanding the hierarchy from generation through transmission to distribution.
- Identify voltage level classifications and their applications
- Explain rationale for voltage transformation
- Calculate power losses at different voltage levels
| Classification | Voltage Range | Application |
|---|---|---|
| Low Voltage (LV) | Up to 1 kV | Residential, commercial |
| Medium Voltage (MV) | 1 - 35 kV | Distribution, industrial |
| High Voltage (HV) | 35 - 230 kV | Sub-transmission |
| Extra High (EHV) | 230 - 765 kV | Bulk transmission |
Power loss in transmission:
For fixed power , doubling voltage halves current, reducing losses to one quarter.
Example: 100 MW at 400 kV vs 11 kV
- At 400 kV: I = 144 A
- At 11 kV: I = 5,249 A (36× higher losses!)
Typical power flow path:
- Generation (11-25 kV)
- Step-up to transmission (275-400 kV)
- Transmission (bulk power transfer)
- Step-down to sub-transmission (132 kV)
- Distribution (33 kV → 11 kV → 400 V)
- Consumer (400 V three-phase / 230 V single-phase)
- MIT OCW - Power System Structure https://ocw.mit.edu/courses/6-061-introduction-to-electric-power-systems-spring-2011/
Per-Unit System
Expressing electrical quantities as fractions of base values to simplify calculations across different voltage levels. Essential skill for all power system analysis.
- Select appropriate base values for power system analysis
- Convert between actual and per-unit quantities
- Perform change-of-base calculations
Quantities expressed as dimensionless fractions of base values:
Advantages:
- Transformer impedances same on both sides
- Equipment values fall in narrow range (0.05-0.15 pu)
- Simplifies hand calculations
Choose two independent bases (typically):
- = 100 MVA (industry standard)
- = Nominal system voltage at each level
Derived bases:
Converting actual impedance to per-unit:
Example: 10 Ω line at 11 kV on 100 MVA base
Converting between different bases:
Used when combining equipment with different nameplate bases.
- Per-Unit System - Open Electrical https://openelectrical.org/index.php?title=Per-unit_System
- NPTEL - Per Unit Calculations https://nptel.ac.in/courses/108105104
Load Flow Analysis
What is Load Flow Analysis
Numerical calculation of steady-state voltages, currents, and power flows throughout a network. The most fundamental power system study, used for planning, operations, and as input to other analyses.
- Set up a load flow problem with correct bus classifications
- Understand purpose and applications of power flow studies
- Identify inputs and outputs of load flow analysis
Answers the question: "Given generation and load, what are the voltages and power flows?"
Calculates:
- Voltage magnitude and angle at each bus
- Real and reactive power flow in each branch
- System losses
- Equipment loading (% of rating)
Each bus must be classified for the solver:
| Type | Known | Unknown | Purpose |
|---|---|---|---|
| Slack (Swing) | V, θ | P, Q | Reference bus, balances system |
| PV (Generator) | P, V | Q, θ | Voltage-controlled generation |
| PQ (Load) | P, Q | V, θ | Most buses - loads and fixed gen |
Typically: 1 slack, few PV, many PQ buses.
- Planning: Assess new generation/transmission options
- Operations: Real-time monitoring and control
- Contingency (N-1): What if a line/generator trips?
- Voltage assessment: Find weak points needing reactive support
- Loss calculation: Optimize power flow paths
- MIT OCW - Power Flow Analysis https://ocw.mit.edu/courses/6-061-introduction-to-electric-power-systems-spring-2011/
- PowerWorld Simulator (Free 13-bus) https://www.powerworld.com/products/simulator
Newton-Raphson and Gauss-Seidel Methods
The two main iterative algorithms for solving load flow equations. Gauss-Seidel is simpler but slower; Newton-Raphson is the industry standard for its speed and robustness.
- Explain conceptual differences between G-S and N-R methods
- Understand why N-R is preferred for large systems
- Interpret convergence behavior and potential issues
Load flow equations are nonlinear (power = V × I, but I depends on V).
No closed-form solution exists for networks with more than a few buses.
Must iterate: guess → calculate → refine → repeat until converged.
Sequential update of each bus voltage:
Pros: Simple to understand and code
Cons: Slow (100+ iterations), poor convergence for large/meshed networks
Use: Small systems, educational purposes
Solves power mismatch equations using Jacobian matrix:
Jacobian structure:
Pros: Fast (3-5 iterations), robust, industry standard
Cons: More complex, requires Jacobian calculation
Simplification of N-R exploiting natural decoupling:
- P-θ: Real power strongly coupled to angles
- Q-V: Reactive power strongly coupled to voltages
Solves two smaller systems instead of one large one. Even faster for transmission networks.
Converged: Mismatches below tolerance (typically 0.001 pu)
Divergence causes:
- Poor initial guess (use flat start: V=1.0, θ=0)
- Excessive reactive demand
- Islanded sections
- Negative impedance (modelling error)
- NPTEL - Load Flow Methods https://nptel.ac.in/courses/108105067
- Pandapower (Python library) https://www.pandapower.org/
Interpreting Load Flow Results
How to read and analyze load flow outputs: voltage profiles, line loadings, losses, and reactive power flows. Identifying problems and potential solutions.
- Analyze voltage profiles and identify violations
- Identify overloaded elements from load flow results
- Calculate and interpret system losses
Plot of voltage magnitude across buses, typically ordered by electrical distance from source.
Acceptable range: Usually 0.95 - 1.05 pu (±5%)
Violations indicate:
- Heavy loading (voltage drop)
- Insufficient reactive support
- Need for tap changer adjustment or capacitor banks
Power flow as percentage of thermal rating:
Watch for:
- >80% - approaching limit, monitor closely
- >100% - overloaded, requires action
Heavily loaded lines are bottlenecks limiting power transfer.
Total real power losses:
Typical values: 2-8% of total generation
Loss breakdown:
- Transmission: ~2-3%
- Distribution: ~4-6%
High losses indicate inefficient power flow paths.
Shows where Q is generated and consumed.
Key observations:
- Generators at Q limits? May need more reactive support
- Long lines consuming Q? Consider series compensation
- Transformers with high Q flow? Check tap positions
Typical load flow output:
| Bus | V (pu) | θ (°) | P (MW) | Q (MVAR) |
|---|---|---|---|---|
| 1 (Slack) | 1.000 | 0.0 | 150.2 | 45.3 |
| 2 (PV) | 1.020 | -2.1 | 80.0 | 23.1 |
| 3 (PQ) | 0.985 | -4.5 | -50.0 | -20.0 |
Negative P/Q = load consuming power
- OpenDSS - Distribution System Simulator https://sourceforge.net/projects/electricdss/
- MATPOWER (MATLAB) https://matpower.org/
Fault Analysis
Types of Faults
Classification of short circuit faults in power systems: three-phase, single line-to-ground, line-to-line, and double line-to-ground. Understanding fault severity and frequency of occurrence.
- Classify fault types from descriptions and diagrams
- Explain which faults are most severe and most common
- Understand sequence network connections for each fault type
All three phases short-circuited together (with or without ground).
Image: Wikimedia Commons, CC BY-SA 3.0
- Severity: Most severe (highest current)
- Frequency: Rarest (~5% of faults)
- Analysis: Simplest - system remains balanced, only positive sequence needed
One phase contacts ground.
- Severity: Depends on grounding (can exceed 3-phase in solidly grounded systems)
- Frequency: Most common (~70-80% of faults)
- Analysis: Requires all three sequence networks in series
Common causes: Lightning, tree contact, insulator flashover
Two phases short-circuited together (not involving ground).
- Severity: ~87% of three-phase fault current
- Frequency: ~15-20% of faults
- Analysis: Positive and negative sequence networks in parallel
Two phases short-circuited together and to ground.
- Severity: Can exceed three-phase in some cases
- Frequency: ~5-10% of faults
- Analysis: Most complex - all sequences in parallel
For solidly grounded systems (typical UK distribution):
For impedance grounded systems:
Three-phase fault is usually used for equipment rating as it's the worst case.
- Circuit Globe - Symmetrical and Unsymmetrical Faults https://circuitglobe.com/symmetrical-and-unsymmetrical-faults.html
Symmetrical Components Theory
Mathematical technique to analyze unbalanced conditions by decomposing into three balanced systems: positive, negative, and zero sequence. Essential for unbalanced fault calculations.
- Convert between phase and sequence quantities
- Draw sequence networks for system components
- Apply correct sequence network connections for different faults
Unbalanced three-phase systems are difficult to analyze directly.
Solution: Decompose into three balanced systems that can be analyzed independently, then recombine.
Invented by Charles Fortescue (1918).
Image: Wikimedia Commons, CC BY-SA 4.0
Positive sequence (1): ABC rotation (normal operating condition)
- Generators produce only positive sequence EMF
Negative sequence (2): ACB rotation (reverse)
- Created by unbalanced conditions
- Causes heating in machines
Zero sequence (0): All three phasors in phase
- Represents ground return current
- Only flows if there's a ground path
Complex operator that rotates by 120°:
Phase to sequence:
Sequence to phase:
For each fault type, connect sequence networks differently:
| Fault | Connection |
|---|---|
| 3-phase | Positive only |
| SLG | All three in series |
| LL | Positive & negative in parallel |
| LLG | All three in parallel |
- SEL - Symmetrical Components Tutorial https://selinc.com/api/download/100688
- NPTEL - Symmetrical Components https://nptel.ac.in/courses/108105067
Fault Levels and Short Circuit Calculations
Calculating fault current magnitude using per-unit and MVA methods. Results used for equipment selection, protection settings, and arc flash studies.
- Calculate fault levels using MVA and per-unit methods
- Select appropriate equipment ratings based on fault levels
- Understand relationship between impedance and fault current
Maximum power (MVA) or current (kA) that flows during a fault at a given point.
Two expressions:
For three-phase fault at a bus:
Usually assume pu.
Example: If total impedance to fault = 0.1 pu:
Quick calculation without per-unit conversion:
Series impedances:
Parallel sources:
Example:
- Grid infeed: 500 MVA
- Transformer: 10% on 20 MVA base → MVA
Ratio of reactance to resistance in fault path.
Importance:
- Determines DC offset decay rate
- Affects peak asymmetrical current
- Higher X/R → slower decay → higher peak
Typical values:
- Transmission: X/R = 15-30
- Distribution: X/R = 5-15
- LV systems: X/R = 2-5
Making current: Peak asymmetrical (first half-cycle)
Breaking current: RMS symmetrical (after few cycles)
Circuit breakers rated for both values.
- Arc Advisor - MVA to kA Conversion https://arcadvisor.com/legacy/mva-ka-conversion
Why Fault Analysis Matters
Applications of fault studies in equipment selection, protection design, safety assessment, and system planning. Understanding how fault levels impact every aspect of power system design.
- Explain importance of fault analysis for safety and equipment
- Relate fault levels to protection coordination
- Understand impact of DG on fault levels
All equipment must withstand fault conditions:
| Equipment | Fault Rating Needed |
|---|---|
| Circuit breakers | Breaking & making capacity |
| Busbars | Short-time withstand (1-3 sec) |
| Cables | Short-circuit rating |
| CTs | Thermal & dynamic limits |
Under-rated equipment can fail catastrophically during faults.
Relay settings require accurate fault currents:
- Pick-up settings: Must detect minimum fault current
- Time grading: Based on fault magnitude variation
- Reach settings: Distance relays need accurate impedances
Wrong fault data = wrong protection = nuisance trips or failure to operate.
Arc flash energy proportional to fault current and duration:
Higher fault level → higher incident energy → more PPE required.
IEEE 1584 standard requires fault study for arc flash assessment.
Adding DG increases fault levels:
- Synchronous generators: Contribute 4-6× rated current
- Inverter-based (solar/wind): Limited to 1.1-1.5× rated
Existing equipment may become under-rated when DG added.
Re-assessment required for any new generation connection.
Key fault calculation standards:
- IEC 60909: International standard, uses voltage factors
- IEEE C37 series: North American practice
- ENA G74: UK-specific for DG connections
IPSA supports IEC 60909 and multiple other methods.
- Coursera - Power System Protection https://www.coursera.org/specializations/power-system-generation-transmission-and-protection
Protection Fundamentals
Protection System Principles
The fundamental requirements of power system protection: speed, selectivity, sensitivity, and reliability. Understanding how protection systems detect faults and isolate them.
- Explain the four key requirements of protection systems
- Understand basic protection system components
- Describe the protection chain from detection to isolation
Detect abnormal conditions and isolate faulted equipment to:
- Protect people from electric shock and arc flash
- Limit equipment damage by clearing faults quickly
- Maintain system stability by preventing cascade failures
- Minimize outage extent by isolating only faulted section
Speed: Clear faults quickly (typically <100ms for transmission)
- Limits equipment damage
- Reduces arc flash energy
- Maintains stability
Selectivity: Only trip the minimum necessary equipment
- Also called "discrimination"
- Faulted section isolated, rest remains energized
Sensitivity: Detect all faults, even low-magnitude ones
- Must see minimum fault current
- Balance with security (avoid nuisance trips)
Security/Reliability: Operate when required, not otherwise
- Dependability: Will operate for genuine faults
- Security: Won't operate for external faults or load
Image: Wtshymanski, Wikimedia Commons, CC BY-SA 3.0
CT (Current Transformer): Measures current, isolates relay from HV
VT (Voltage Transformer): Measures voltage, provides isolation
Relay: Processes CT/VT signals, makes trip decision
Circuit Breaker: Interrupts fault current
DC Supply: Battery-backed power for relays and trip coils
Fault → CT/VT detect → Relay processes → Trip signal → Breaker opens
Typical times:
- Relay operation: 20-40 ms
- Breaker operation: 40-80 ms
- Total clearance: 60-120 ms (transmission)
- Distribution: up to 500 ms+ (for coordination)
- NPTEL - Power System Protection https://nptel.ac.in/courses/108105104
Protection Relay Types
The main types of protection relays: overcurrent, distance, and differential. Understanding operating principles and applications for each type.
- Explain operating principle of each relay type
- Select appropriate relay type for different applications
- Understand ANSI device numbering system
Trips when current exceeds a threshold.
50 - Instantaneous: Fixed time, high pickup
- Typically set to see close-in faults only
- Operates in 20-50 ms
51 - Time Overcurrent: Inverse time characteristic
- Higher current = faster operation
- Allows coordination with downstream devices
Application: Distribution networks, motor protection, backup protection
Inverse Definite Minimum Time curves:
Image: Wikimedia Commons, CC BY-SA 4.0
Where:
- TMS = Time Multiplier Setting
- = Pick-up current setting
- k, α = curve constants
| Curve | k | α |
|---|---|---|
| Standard Inverse (SI) | 0.14 | 0.02 |
| Very Inverse (VI) | 13.5 | 1.0 |
| Extremely Inverse (EI) | 80 | 2.0 |
VI/EI used where fault current varies significantly with location.
Measures impedance (Z = V/I) to determine fault location.
Zones:
- Zone 1: 80-85% of line, instantaneous
- Zone 2: 100-120% of line, ~0.3s delay
- Zone 3: 150-200%, backup, ~1s delay
Application: Transmission line protection
Compares current entering vs leaving protected zone.
If difference exceeds threshold → internal fault → trip.
Key property: 100% selective - only operates for internal faults
Applications:
- Transformer (87T)
- Generator (87G)
- Busbar (87B)
- Motor (87M)
Standard numbering for protection functions:
| Number | Function |
|---|---|
| 21 | Distance |
| 25 | Synch check |
| 27 | Undervoltage |
| 50 | Instantaneous OC |
| 51 | Time OC |
| 59 | Overvoltage |
| 67 | Directional OC |
| 81 | Frequency |
| 87 | Differential |
Suffix letters: N=neutral, G=ground, T=transformer
- PAC Basics - Protection Fundamentals https://pacbasics.org/
- GE Multilin - Relay School https://www.gegridsolutions.com/multilin/
Protection Coordination
Designing protection systems so that only the device nearest the fault operates, minimizing the extent of the outage. Time grading, current grading, and coordination principles.
- Design coordinated protection schemes
- Calculate coordination time intervals
- Select appropriate IDMT curve characteristics
Goal: Only the device closest to the fault should operate.
If fault at point F:
Source ──[A]──[B]──[C]── F ──[Load]
Relay C should trip first. If C fails, B backs up. If B fails, A backs up.
Achieved through time grading and/or current grading.
Upstream devices have progressively longer delays.
Coordination Time Interval (CTI): 0.3 - 0.5 seconds
Accounts for:
- Breaker operating time (~50-80 ms)
- Relay overshoot (~50 ms)
- Safety margin (~100 ms)
Example:
- Relay C: 0.1s at max fault
- Relay B: 0.1 + 0.4 = 0.5s
- Relay A: 0.5 + 0.4 = 0.9s
Use fault current magnitude differences to discriminate.
Fault current decreases with distance from source due to line impedance.
Set instantaneous elements (50) to see only close-in faults:
Limitation: Doesn't work well on short feeders or where fault current doesn't vary much.
For IDMT relays, check coordination at maximum fault current through both devices:
- Calculate downstream relay time at max fault
- Add CTI (0.3-0.5s)
- Calculate upstream TMS to achieve this time
Parallel feeders: Both see same fault current - need directional elements (67)
Ring networks: Fault current from both directions - need directional or differential
DG infeed: Changes fault current magnitude and direction
Motor contribution: Adds to fault current, decays quickly
- Coursera - Protection Coordination https://www.coursera.org/specializations/power-system-generation-transmission-and-protection
Time-Current Curves
Graphical representation of protection device characteristics. How to plot, read, and use TCCs for coordination studies.
- Construct and interpret TCC plots
- Identify coordination margins and problems
- Verify protection against equipment damage curves
Log-log plot showing operating time vs current.
Axes:
- X-axis: Current (log scale), usually in Amps
- Y-axis: Time (log scale), in seconds
Why log-log? Covers wide ranges (0.01s to 1000s, 10A to 100kA)
Fuses: Show as bands (two lines)
- Left line: Minimum melting time
- Right line: Total clearing time
Relays: Show as single lines (adjustable)
- Family of curves for different TMS settings
Breakers: Vertical lines at:
- Continuous rating
- Instantaneous trip (if equipped)
Rules for proper coordination:
- Downstream curve must be below and left of upstream
- Maintain CTI gap at all fault current levels
- Check at both minimum and maximum fault points
Crossover: Where curves intersect = loss of coordination
Equipment withstand limits plotted on same TCC:
Cable damage curve: Where k depends on conductor material and insulation
Transformer: Inrush point and thermal damage
Motor: Starting current and locked rotor time
Rule: Protective device curve must be left of damage curve (faster operation).
Reading a coordination study:
Time (s)
1000 |
100 | [Upstream Relay]
10 | [Downstream Relay]
1 |
0.1 | [Fuse]
0.01 |_________________________
10 100 1k 10k Current (A)
Check gaps between curves at fault current levels.
- ETAP TCC Tutorial https://etap.com/
Protection Zones and Backup
Dividing the power system into protection zones with overlapping boundaries. Primary and backup protection philosophy to ensure no blind spots.
- Define protection zones for power system components
- Design primary and backup protection schemes
- Understand zone overlap at circuit breakers
A zone is an area of the network protected by a specific relay or set of relays.
Zone boundaries defined by CT locations.
Principle: Every element must be within at least one zone.
Zones should overlap at circuit breakers to avoid blind spots.
Zone A Zone B
|<────────────>|<────────────>|
CT CB CT
Fault at CB location seen by both zones - both may trip (acceptable for reliability).
First line of defense for a zone.
Characteristics:
- Fast operation (instantaneous or Zone 1)
- Highly selective (only for internal faults)
- Examples: Differential (87), Distance Zone 1 (21)
Should clear ~90% of faults.
Local backup: Duplicate protection within same zone
- Same speed and selectivity as primary
- Protects against relay/CT failure
- Example: Dual main protections
Remote backup: Protection from adjacent zones
- Slower (time-delayed)
- Less selective (trips more than necessary)
- Example: Distance Zone 2/3, time-graded overcurrent
| Equipment | Primary | Backup |
|---|---|---|
| Transmission line | Distance (21) | Distance Z2/Z3, OC |
| Transformer | Differential (87T) | Overcurrent (51), REF |
| Busbar | Differential (87B) | Breaker fail, remote |
| Generator | Differential (87G) | Overcurrent, loss of excitation |
| Motor | Thermal (49), Diff | Overcurrent (51) |
What if the breaker doesn't open?
Breaker Failure (50BF):
- Trip signal sent to breaker
- Timer starts (typically 150-200ms)
- If fault current still flowing → trip all adjacent breakers
Last resort backup - isolates larger area but prevents catastrophic failure.
- IEEE - Protection Zones https://ieeexplore.ieee.org/document/9640382/
- Electrical Axis - Zones of Protection http://www.electricalaxis.com/
Network Components
Transformers in Power Networks
Power transformers for voltage transformation: ratings, impedance, tap changers, and vector groups. Understanding how transformer parameters affect load flow and fault studies.
- Specify transformer ratings, impedances, and vector groups
- Understand tap changer operation and voltage regulation
- Calculate fault current contribution through transformers
Image: Wikimedia Commons, CC BY-SA 3.0
Voltage transformation by turns ratio:
Ratings specified:
- MVA (apparent power)
- Primary/secondary voltage (kV)
- Impedance (%Z on rating)
- Vector group
Impedance limits fault current and causes voltage drop.
Typical values:
- Distribution (11/0.4kV): 4-6%
- Primary (33/11kV): 7-10%
- Transmission (132/33kV): 10-15%
Fault current through transformer:
Example: 10% impedance → fault current = 10× rated
Adjust turns ratio to regulate voltage.
OLTC (On-Load Tap Changer):
- Changes taps without interrupting load
- Typical range: ±10% in 1.25% or 1.67% steps
- Located on HV winding (lower current)
- Automatic voltage regulation (AVR) control
Off-circuit tap changer:
- Must de-energize to change
- Used for fixed adjustment only

Image: Wikimedia Commons
Notation describes winding connections and phase shift.
Letters:
- D/d = Delta
- Y/y = Star (Wye)
- N/n = Neutral brought out
- Capital = HV, lowercase = LV
Number: Phase shift in clock hours (× 30°)
Common groups:
| Group | Shift | Application |
|---|---|---|
| Dyn11 | -30° | Distribution |
| YNd1 | +30° | Generator step-up |
| Yy0 | 0° | Auto-transformer |
Transformers in parallel must have:
- Same vector group (or compatible: Dy1 with Dy1)
- Same voltage ratio (within tap range)
- Similar impedance (within 10% for load sharing)
Mismatched vector groups → circulating currents → overheating
- The Engineering Mindset - Electrical https://theengineeringmindset.com/electrical/
- Electrical4U - Vector Groups https://www.electrical4u.com/vector-group-of-transformer/
Cables and Underground Lines
Power cable construction, impedance characteristics, current ratings, and voltage drop calculations. Derating factors for installation conditions.
- Calculate cable sizing for ampacity and voltage drop
- Apply derating factors for installation conditions
- Understand cable impedance characteristics
Image: Wikimedia Commons, CC BY-SA 3.0
Layers (inside out):
- Conductor (copper or aluminium)
- Conductor screen
- Insulation (XLPE, EPR, or PVC)
- Insulation screen
- Metallic sheath/screen
- Outer sheath (PE or PVC)
Insulation temperature limits:
- XLPE: 90°C continuous, 250°C short-circuit
- PVC: 70°C continuous
Cables have higher R/X ratio than overhead lines.
Typical values at 50Hz:
| Cable | R (Ω/km) | X (Ω/km) | R/X |
|---|---|---|---|
| LV 185mm² | 0.164 | 0.073 | 2.2 |
| 11kV 185mm² | 0.164 | 0.090 | 1.8 |
| 33kV 300mm² | 0.060 | 0.110 | 0.5 |
High R/X ratio means voltage drop dominated by real power at LV.
Maximum continuous current limited by:
- Conductor temperature
- Insulation thermal limits
- Heat dissipation (installation method)
Base rating from manufacturer tables, then apply derating:
| Factor | Description | Typical Range |
|---|---|---|
| Ambient temperature | 0.7 - 1.1 | |
| Grouping (multiple cables) | 0.6 - 1.0 | |
| Soil thermal resistivity | 0.8 - 1.0 | |
| Depth of burial | 0.95 - 1.0 |
Example: 400A base × 0.9 × 0.7 × 0.95 × 0.98 = 235A
Three-phase voltage drop:
Where:
- I = current (A)
- L = length (m)
- R, X = resistance, reactance (Ω/km)
UK limits (BS 7671):
- Lighting: 3%
- Other: 5%
- Total from origin: 5%
- BS 7671 Cable Sizing Guide https://electrical.theiet.org/
- Nexans Cable Calculator https://www.nexans.co.uk/
Overhead Lines
Transmission and distribution overhead line characteristics: impedance, thermal ratings, sag considerations, and comparison with cables.
- Calculate overhead line impedance
- Understand thermal rating methods (static vs dynamic)
- Compare overhead lines with underground cables

Image: Wikimedia Commons, CC BY-SA 4.0
Conductor types:
- ACSR: Aluminium Conductor Steel Reinforced
- AAAC: All Aluminium Alloy Conductor
- HTLS: High Temperature Low Sag (for uprating)
Typical spans:
- Distribution: 50-150m
- Transmission: 300-500m
Overhead lines have lower R/X ratio than cables.
Typical values (per km):
| Line | R (Ω/km) | X (Ω/km) | R/X |
|---|---|---|---|
| 11kV distribution | 0.3 | 0.35 | 0.9 |
| 33kV | 0.12 | 0.38 | 0.3 |
| 132kV | 0.06 | 0.40 | 0.15 |
| 400kV | 0.03 | 0.32 | 0.1 |
Higher X due to wider conductor spacing (air insulation).
Current limited by conductor temperature (sag limit or annealing).
Static rating: Conservative fixed value
- Assumes: high ambient, full sun, low wind
- Typically 50-75% of actual capacity
Dynamic Line Rating (DLR): Real-time calculation
- Uses weather data (wind, ambient, solar)
- Can increase capacity 10-30%
- Requires monitoring equipment
Conductor sag increases with:
- Temperature (thermal expansion)
- Current (resistive heating)
- Ice loading (weight)
Sag formula (parabolic approximation):
Where:
- w = weight per unit length
- L = span length
- T = conductor tension
Clearance requirements (to ground, buildings, other lines) set maximum allowable sag.
| Aspect | Overhead Line | Cable |
|---|---|---|
| Capital cost | Lower (5-10×) | Higher |
| Maintenance | Higher | Lower |
| Visual impact | High | None |
| Reliability | Weather-affected | Protected |
| Fault rate | Higher | Lower |
| Repair time | Faster | Slower |
| Reactive power | Generates (line charging) | Consumes |
| Urban use | Limited | Preferred |
- US DOE - Dynamic Line Rating https://www.energy.gov/oe/articles/dynamic-line-rating-report-congress-june-2019
- IEEE 738 - Line Rating Calculation https://standards.ieee.org/
Generators and Synchronous Machines
Synchronous generator characteristics, capability curves, and reactive power control. Understanding generator contribution to fault current and voltage regulation.
- Interpret generator capability curves
- Understand excitation control and reactive power
- Calculate generator fault current contribution

Image: Wikimedia Commons, Public Domain
Speed-frequency relationship:
Where:
- f = frequency (Hz)
- P = number of poles
- N = speed (rpm)
For 50Hz: 2-pole = 3000rpm, 4-pole = 1500rpm
Multiple reactances for different timescales:
| Reactance | Symbol | Typical (pu) | Timescale |
|---|---|---|---|
| Sub-transient | 0.1-0.25 | 0-50ms | |
| Transient | 0.15-0.35 | 50ms-2s | |
| Synchronous | 1.0-2.5 | Steady-state |
Fault studies use for maximum (initial) fault current.
Image: Wikimedia Commons, CC BY-SA 4.0
P-Q diagram showing operating limits:
Limits:
- Right arc: Armature current (MVA rating)
- Top arc: Field current (over-excitation)
- Bottom curve: Stator end heating (under-excitation)
- Vertical line: Prime mover (MW limit)
Generator can operate anywhere inside the curve.
Field current controls reactive power output:
Over-excited: High field current → exports Q → supports voltage
Under-excited: Low field current → absorbs Q → may depress voltage
AVR (Automatic Voltage Regulator):
- Maintains terminal voltage setpoint
- Adjusts field current automatically
- Droop setting for load sharing
In load flow analysis:
PV mode (voltage control):
- P and V specified
- Q calculated (within limits)
- Normal operation
PQ mode (fixed output):
- P and Q both specified
- V calculated
- Used when at reactive limit
Slack bus:
- V and θ specified (reference)
- P and Q calculated
- Balances system losses
Generator fault current decays over time:
(sub-transient, first few cycles)
(transient, up to ~2 seconds)
(steady-state, if fault sustained)
Typical contribution: 4-6× rated current initially
- NPTEL - Synchronous Machines https://nptel.ac.in/courses/108105017
- All About Circuits - Synchronous Generators https://www.allaboutcircuits.com/
Distributed Generation
How Renewables Connect to the Grid
Grid connection architectures for solar PV and wind generation. Understanding inverter-based resources, transformer requirements, and connection voltage selection.
- Describe grid connection architectures for solar and wind
- Understand inverter-based resource characteristics
- Select appropriate connection voltage for different capacities

Image: Wikimedia Commons, CC BY-SA 3.0
Connection chain:
PV Panels (DC) → Inverter (DC/AC) → Transformer → Grid
Inverter functions:
- DC to AC conversion
- Maximum Power Point Tracking (MPPT)
- Grid synchronisation
- Power factor control
- Anti-islanding protection
Image: Arne Nordmann, Wikimedia Commons, CC BY-SA 2.5
Two main types:
DFIG (Doubly-Fed Induction Generator):
- Partial converter (30% rating)
- Limited fault ride-through
- Older technology
Full Converter:
- 100% power through converter
- Better fault ride-through
- Decoupled from grid frequency
- Modern standard
Voltage level based on capacity:
| Capacity | Typical Voltage | Connection |
|---|---|---|
| <50 kW | 400V (LV) | Single premises |
| 50kW - 1MW | 400V or 11kV | LV or HV feeder |
| 1 - 10 MW | 11kV or 33kV | Primary substation |
| 10 - 50 MW | 33kV or 132kV | BSP or GSP |
| >50 MW | 132kV+ | Transmission |
DNO specifies minimum connection voltage in offer.
Key differences from synchronous machines:
| Aspect | Synchronous | Inverter |
|---|---|---|
| Inertia | Yes (rotating mass) | No (virtual possible) |
| Fault current | 4-6× rated | 1.1-1.5× rated |
| Frequency response | Inherent | Programmed |
| Reactive capability | Full range | Limited by rating |
Grid-forming vs Grid-following:
- Grid-following: Needs grid voltage reference
- Grid-forming: Can establish voltage/frequency (emerging)
Typical DG connection includes:
- Inverter(s) with protection settings
- LV switchboard with metering
- Transformer (if HV connection)
- HV switchgear (ring main unit or circuit breaker)
- G99 protection relay (interface protection)
- Metering (import/export, half-hourly)
- IET - Grid Connection of Solar PV https://electrical.theiet.org/
- RenewableUK - Wind Energy https://www.renewableuk.com/
UK Grid Code Compliance (G99/G100)
UK requirements for connecting generation to distribution networks. Engineering Recommendation G99 classifications, technical requirements, and the connection application process.
- Classify generators by G99 type
- Understand key technical requirements
- Navigate UK connection application process
Engineering Recommendation G99 (replaced G59 in 2019)
Aligns UK with EU Requirements for Generators (RfG).
Applies to all new generation connecting to distribution networks (up to 132kV).
Key document: ENA Engineering Recommendation G99
Based on capacity and connection voltage:
| Type | Capacity | Voltage | Requirements |
|---|---|---|---|
| A | 0.8kW - 1MW | <110kV | Basic |
| B | 1 - 10 MW | <110kV | Intermediate |
| C | 10 - 50 MW | <110kV | Advanced |
| D | ≥50 MW or ≥110kV | Any | Full compliance |
Higher types have more onerous requirements.
Frequency response:
- LFSM-O: Reduce output above 50.4Hz
- LFSM-U: Maintain output down to 47.5Hz
- FSM: Optional fast frequency response
Voltage ride-through:
- Must stay connected during voltage dips
- Type-dependent duration and depth
Reactive capability:
- Power factor range (typically 0.95 lag to 0.95 lead)
- Voltage control modes
Protection settings:
- Over/under frequency and voltage
- Rate of Change of Frequency (RoCoF)
- Vector shift (Loss of Mains)
G100 allows connection where network capacity is limited.
Active Network Management (ANM):
- Real-time curtailment signals
- Generator reduces output when network constrained
- Enables more DG without reinforcement
Principle of Access:
- Last-in, first-off (LIFO)
- Or pro-rata sharing
Steps to connect:
- Application: Submit G99 form A to DNO
- Assessment: DNO studies impact (4-12 weeks)
- Offer: Connection offer with costs and timescales
- Acceptance: Sign agreement, pay charges
- Design: Detailed design and approval
- Construction: Install equipment
- Commissioning: Witness tests, settings verification
- Energisation: Final Operating Notification (FON)
Typical timescales: 3-18 months depending on complexity
- ENA - Engineering Recommendations https://www.energynetworks.org/
- National Grid ESO - Grid Code https://www.neso.energy/industry-information/codes/
Voltage Rise from Embedded Generation
How distributed generation causes voltage rise on distribution networks, calculation methods, and mitigation strategies. A key constraint on DG hosting capacity.
- Calculate voltage rise from DG connections
- Understand R/X ratio effects at different voltage levels
- Design mitigation strategies
Traditional networks designed for one-way power flow:
Substation → Feeder → Loads
(Voltage drops along feeder)
With DG, power can flow backwards:
Substation ← DG export
(Voltage rises at DG location)
Voltage may exceed statutory limits (+10% / -6% in UK).
Approximate voltage change from injected power:
Where:
- P, Q = active/reactive power injection
- R, X = resistance/reactance to source
- V = nominal voltage
In per-unit:
| Network | R/X Ratio | Dominant Factor |
|---|---|---|
| LV (400V) | 2-5 | Active power (P) |
| 11kV | 1-2 | Both P and Q |
| 33kV | 0.3-0.5 | Reactive power (Q) |
| 132kV | 0.1-0.2 | Reactive power (Q) |
Key insight: At LV, voltage rise mainly from real power export.
Reactive power absorption has limited effect on LV voltage.
Statutory limits (ESQCR):
- LV: 230V +10% / -6% (216V to 253V)
- HV: ±6% of nominal
DNO planning limits (more conservative):
- Typically allow +3% rise from DG at minimum load
- Ensures headroom for voltage regulation
Network solutions:
- Conductor upgrades (reduce R)
- New transformer (reduce impedance)
- Voltage regulators / boosters
DG solutions:
- Reactive power absorption (Q negative)
- Power factor control (limited at LV)
- Active power curtailment
- Export limiting (G100)
Smart solutions:
- OLTC coordinated control
- Active Network Management (ANM)
- Battery storage for peak shaving
- IET - Voltage Rise Calculations https://electrical.theiet.org/
- Western Power Distribution - DG Connections https://www.nationalgrid.co.uk/
Anti-Islanding Protection
Preventing distributed generation from energising an isolated section of network. Detection methods, protection settings, and UK requirements for Loss of Mains protection.
- Explain islanding hazards
- Specify anti-islanding protection settings
- Design Loss of Mains protection schemes
Image: Wikimedia Commons, CC BY-SA 4.0
Islanding: DG continues to energise a section of network that has been disconnected from the main grid.
Can occur when:
- Upstream breaker opens (fault, maintenance)
- DG output matches local load (balanced island)
Safety:
- Network assumed dead may be live
- Risk to personnel working on "isolated" network
- Public contact with downed conductors
Equipment:
- Poor power quality (voltage/frequency drift)
- Out-of-phase reclosing (severe damage)
- Fault clearance failure (no grid fault current)
Requirement: Disconnect within 2 seconds of island forming.
Detect abnormal conditions caused by islanding:
| Method | Setting | Notes |
|---|---|---|
| Under-voltage (27) | 0.8 pu | 0.5s delay |
| Over-voltage (59) | 1.1 pu | 1.0s delay |
| Under-frequency (81U) | 47.5 Hz | 0.5s delay |
| Over-frequency (81O) | 52 Hz | 0.5s delay |
| RoCoF (81R) | 1.0 Hz/s | 0.5s delay |
| Vector Shift (VS) | 6° | Instantaneous |
Limitation: May not detect balanced island (generation = load).
Inverter deliberately perturbs output to detect island:
Frequency shift: Slight bias causes runaway if islanded
Reactive power variation: Inject Q pulses, monitor V response
Impedance measurement: Inject signal, measure grid impedance
More reliable than passive methods but can interact between multiple inverters.
Loss of Mains (LoM) protection settings:
| Protection | Setting | Delay |
|---|---|---|
| Under-frequency | 47.5 Hz | 0.5s |
| Over-frequency | 52.0 Hz | 0.5s |
| Under-voltage | 0.8 pu | 2.5s |
| Over-voltage | 1.1 pu | 1.0s |
| RoCoF | 1.0 Hz/s | 0.5s |
Note: RoCoF settings relaxed from 0.125 Hz/s to 1.0 Hz/s to improve stability with low inertia.
Vector shift generally not used in UK (nuisance tripping).
G99-compliant protection relay provides:
- Voltage and frequency protection (27, 59, 81)
- RoCoF protection (df/dt)
- Intertrip receive (from DNO)
- Status monitoring and event logging
Must be type-tested to G99 requirements.
Common manufacturers: Woodward, Schneider, ABB, Siemens
- ENA - Loss of Mains Protection https://www.energynetworks.org/
- IEEE 1547 - DG Interconnection https://standards.ieee.org/
UK Power System
UK Network Structure
Organisation of the GB electricity system: the system operator (NESO), transmission owners, and distribution network operators. Understanding roles, responsibilities, and regulatory framework.
- Identify roles of NESO, transmission owners, and DNOs
- Understand UK regulatory framework
- Navigate industry organisation structure
Image: Wikimedia Commons, CC BY-SA 3.0
Great Britain has a unified synchronous grid covering England, Wales, and Scotland.
Northern Ireland is part of the all-island Irish system (connected via HVDC).
Key principle: Separation of system operation from asset ownership.
NESO (formerly National Grid ESO, separated October 2024)
Role: Balances supply and demand in real-time
Responsibilities:
- Frequency control (maintain 50Hz ± 0.5Hz)
- Voltage management
- Constraint management
- Balancing mechanism operation
- Future Energy Scenarios (FES)
- Network planning and connections
Not an asset owner - operates the system impartially.
Own and maintain the high-voltage transmission network:
| TO | Area | Voltages |
|---|---|---|
| NGET | England & Wales | 275kV, 400kV |
| SP Transmission | Southern Scotland | 132kV, 275kV, 400kV |
| SHET (SSE) | Northern Scotland | 132kV, 275kV |
Note: 132kV is transmission in Scotland, distribution in England & Wales.
Regulated by Ofgem under RIIO-T2 price control.
Own and operate local distribution networks:
| DNO Group | Operating Areas |
|---|---|
| UK Power Networks | London, East, South East |
| National Grid ED | Midlands, South West, South Wales |
| SP Energy Networks | Merseyside, North Wales, Central/Southern Scotland |
| SSE Networks | Northern Scotland, Southern England |
| Northern Powergrid | North East, Yorkshire |
| Electricity North West | North West England |
14 licensed DNO areas across GB.
Regulated under RIIO-ED2 price control.
Ofgem: Independent regulator
- Sets price controls (allowed revenues)
- Enforces licence conditions
- Protects consumer interests
ELEXON: Settlement body
- Balancing and Settlement Code (BSC)
- Calculates imbalance charges
Energy Networks Association (ENA):
- Industry body for network operators
- Publishes Engineering Recommendations (G99, P28, etc.)
- National Grid ESO - About Us https://www.neso.energy/
- Ofgem - Network Regulation https://www.ofgem.gov.uk/
UK Voltage Levels
Standard voltage levels used in the GB power system from 400kV transmission down to 230V consumer supply. Understanding the hierarchy and interface points between networks.
- Identify UK voltage levels and their applications
- Understand substation hierarchy and interface points
- Select appropriate voltage for different connections
Supergrid (England & Wales):
- 400kV - Main bulk transmission
- 275kV - Older transmission, some areas
Scotland:
- 400kV, 275kV - Main transmission
- 132kV - Transmission (not distribution)
Interconnectors:
- HVDC links to France, Netherlands, Belgium, Norway, Ireland
- Typically ±320kV to ±525kV DC
| Voltage | Name | Typical Use |
|---|---|---|
| 132kV | EHV (E&W only) | Grid Supply Points, large industrial |
| 33kV | HV | Primary distribution, bulk supply |
| 11kV | HV | Secondary distribution, commercial |
| 6.6kV | HV | Some older urban networks |
| 400V | LV (3-phase) | Commercial, small industrial |
| 230V | LV (1-phase) | Domestic consumers |
Note: Some areas have 20kV or 22kV instead of 11kV.
Grid Supply Point (GSP):
- Transmission to distribution interface
- 400kV/275kV → 132kV (or 33kV in some areas)
- Metering point for settlement
Bulk Supply Point (BSP):
- 132kV → 33kV transformation
- Feeds multiple primary substations
Primary Substation:
- 33kV → 11kV transformation
- Feeds HV distribution network
Secondary Substation (Distribution):
- 11kV → 400V transformation
- Pole-mounted or ground-mounted
- Feeds LV network to consumers
Typical voltage hierarchy:
400kV ──┬── GSP
│
132kV ──┼── BSP
│
33kV ──┼── Primary
│
11kV ──┼── Secondary
│
400V ───┴── Consumer
Each step typically has 2-3 transformers for redundancy.
Nominal voltage: System design voltage (e.g., 11kV, 400V)
Declared voltage: What supplier declares to customers
- LV: 230V (was 240V until 1995 harmonisation)
- Tolerance: +10% / -6% (216V to 253V)
Historical note: UK moved from 240V ±6% to 230V +10%/-6%, effectively the same range but aligned with European standard.
- ENA - Electricity Networks Overview https://www.energynetworks.org/
- National Grid - Network Route Maps https://www.nationalgrid.com/
UK Standards and Engineering Recommendations
Key technical standards governing UK power system design and operation. Engineering Recommendations for connections, power quality, and planning standards.
- Apply relevant Engineering Recommendations to projects
- Assess power quality compliance (flicker, harmonics, unbalance)
- Navigate UK connection requirements
Engineering Recommendations (ERECs) published by ENA:
Industry-agreed technical standards for:
- Generator connections (G-series)
- Power quality (P-series)
- Design and planning (various)
Not legally binding but effectively mandatory via DNO connection agreements.
G99: Requirements for connection of generation equipment
Replaced G59 (large) and G83 (small) in April 2019.
Scope: All generation 0.8kW to 50MW connecting at <110kV
Key requirements:
- Frequency and voltage ride-through
- Reactive capability
- Protection settings (LoM, over/under V & f)
- Compliance process and testing
See earlier topic on G99 for details.
G100: Technical requirements for export limiting schemes
Allows connection where network capacity limited:
- ANM (Active Network Management): Real-time curtailment
- Export limiting: Fixed maximum export
- Timed connections: Export only at certain times
Enables more DG without costly reinforcement.
P28: Planning limits for voltage fluctuations
Flicker: Rapid voltage variations causing visible light flicker
Limits:
- Short-term severity
- Long-term severity
- Step changes (frequent) or 6% (infrequent)
Causes: Motor starting, arc furnaces, wind turbines
Assessment: Required for large loads or generation connections
P29: Planning limits for voltage unbalance
Unbalance: Difference between phase voltages
Where = negative sequence, = positive sequence
Limits:
- Planning level: 1.3%
- Compatibility level: 2.0%
Causes: Single-phase loads, unbalanced three-phase loads
G5/4-1: Planning levels for harmonic voltage distortion
THD (Total Harmonic Distortion):
Planning limits (% of fundamental):
| Voltage | THD | Individual (odd) |
|---|---|---|
| LV | 5% | 4-5% |
| MV (11-33kV) | 4% | 3-4% |
| HV (132kV) | 3% | 2-3% |
Causes: Power electronics, VFDs, rectifiers, LED lighting
Security standards:
- SQSS: Security and Quality of Supply Standard (transmission)
- P2/6: Security of supply (distribution) - being replaced by P2/8
Design standards:
- BS 7671: Wiring Regulations (LV installations)
- ENA TS 41-24: Guidelines for LV connections
Grid codes:
- Grid Code: Transmission-connected parties
- Distribution Code: Distribution-connected parties
- CUSC: Connection and Use of System Code
- ENA - Engineering Recommendations https://www.energynetworks.org/industry-hub/resource-library
- National Grid ESO - Grid Code https://www.neso.energy/industry-information/codes/grid-code
UK System Operation Basics
How the GB electricity system is balanced in real-time. Understanding frequency control, the balancing mechanism, and constraint management.
- Explain how system frequency is maintained
- Understand the balancing mechanism basics
- Describe constraint management approaches
Target: 50.00 Hz ± 0.2 Hz (normal operating range)
Frequency rises when generation > demand Frequency falls when demand > generation
Response services:
| Service | Speed | Duration |
|---|---|---|
| Inertia | Instantaneous | Seconds |
| Primary response | 10 seconds | 30 seconds |
| Secondary response | 30 seconds | 30 minutes |
| Tertiary / reserve | Minutes | Hours |
NESO procures these services from generators and batteries.
BM: Real-time market for balancing
How it works:
- Generators/suppliers submit bids and offers
- Bid: Price to reduce output (or increase demand)
- Offer: Price to increase output (or reduce demand)
- NESO accepts bids/offers to balance system
- Settled at bid/offer price (pay-as-bid)
Gate closure: 1 hour before delivery
Imbalance price: Cash-out for parties not in balance
Constraint: When power flow exceeds line/transformer rating
Causes:
- High renewable output in weak areas
- Outages reducing network capacity
- Demand patterns
Actions:
- Re-dispatch generation (BM actions)
- Curtail wind/solar
- Intertrips (automatic post-fault)
Constraint costs: £500M+ annually (growing with renewables)
NESO forecasts demand to plan generation:
Timescales:
- Week ahead: Unit commitment
- Day ahead: Final schedules
- Intraday: Adjustments
- Real-time: Balancing actions
Factors:
- Weather (temperature, wind, solar)
- Time of day/week/year
- TV pickups (kettles at half-time!)
- Bank holidays
- COVID showed how much patterns can change
System operation becoming more complex:
Low inertia:
- Less synchronous generation
- Faster frequency changes
- Need for synthetic inertia from batteries/IBRs
Variable renewables:
- High instantaneous penetration (>70% at times)
- Need for flexibility (storage, DSR, interconnectors)
Distributed resources:
- Millions of small generators/batteries
- Visibility challenge for NESO
- Local vs national balancing
- National Grid ESO - Balancing Services https://www.neso.energy/industry-information/balancing-services
- ELEXON - Imbalance Pricing https://www.elexon.co.uk/
- Grid Watch - Live GB Grid Data https://gridwatch.co.uk/