Distributed Generation
eee-roadmap.muhammadhazimiyusri.uk/roadmaps/distributed-generation/
Distributed Generation Basics
Domestic Generation Overview
Introduction to small-scale power generation at homes and buildings. Covers solar PV, small wind, and battery storage systems. Understand why distributed generation is growing and its role in the energy transition.
- Identify common domestic generation technologies
- Understand the difference between grid-tied and off-grid systems
- Explain the benefits and challenges of distributed generation
Photovoltaic Effect Fundamentals
Solar photovoltaic (PV) systems convert sunlight directly into electricity using semiconductor materials. When photons strike a PV cell, they excite electrons in the semiconductor material, creating electron-hole pairs. The built-in electric field of the p-n junction separates these charge carriers, producing direct current.
Cell Types and Characteristics
| Cell Type | Efficiency | Characteristics |
|---|---|---|
| Monocrystalline | 17-22% | Uniform dark appearance, highest efficiency |
| Polycrystalline | 15-18% | Blue speckled appearance, good value |
| Thin-film | 10-13% | Flexible, lower cost per watt |
Series and Parallel Configurations
Modules in series increase voltage while maintaining current: $$V_{string} = n \times V_{module}$$ $$I_{string} = I_{module}$$
Modules in parallel increase current while maintaining voltage: $$V_{array} = V_{module}$$ $$I_{array} = n \times I_{module}$$
I-V Curve and Key Parameters
The current-voltage relationship follows the diode equation. Key points:
- Short-circuit current ($I_{SC}$): Maximum current when V = 0
- Open-circuit voltage ($V_{OC}$): Maximum voltage when I = 0
- Maximum Power Point (MPP): Where is maximized
Fill Factor
Fill factor quantifies how "square" the I-V curve is: $$FF = \frac{V_{MPP} \times I_{MPP}}{V_{OC} \times I_{SC}} = \frac{P_{max}}{V_{OC} \times I_{SC}}$$
Typical values: 0.7-0.85 for crystalline silicon cells.
Module Efficiency
Where = irradiance (W/m²) and = module area (m²).
Battery Types for Energy Storage
| Chemistry | Voltage | Energy Density | Cycle Life |
|---|---|---|---|
| Lithium-ion (NMC) | 3.6-3.7V | 150-250 Wh/kg | 1000-2000 |
| LiFePO4 (LFP) | 3.2V | 90-120 Wh/kg | 2000-5000 |
| Lead-acid | 2.0V | 30-50 Wh/kg | 500-1000 |
Capacity Calculations
Amp-hour capacity (Ah):
Energy capacity (kWh):
C-Rate
C-rate defines charge/discharge rate relative to capacity: $$\text{C-rate} = \frac{I_{charge/discharge}}{C_{rated}}$$
A 100Ah battery at 1C discharges at 100A (fully discharged in 1 hour). At 0.5C: 50A (2 hours). At 2C: 200A (30 minutes).
Depth of Discharge (DoD) and State of Charge (SoC)
Usable Capacity
For LFP batteries with 90% usable DoD:
Round-trip Efficiency
Typical values: Li-ion 86-88%, Lead-acid 79-85%.
Grid-tied (On-Grid) Systems
Grid-tied systems operate in parallel with the utility network.
Architecture: PV array → Grid-tie inverter → AC panel → Utility meter → Grid
Advantages:
- Lower initial cost (no batteries)
- Higher overall efficiency
- Net metering benefits
- Grid acts as infinite "storage"
Limitations:
- No backup during outages (anti-islanding protection)
- Subject to grid regulations and export limits
Off-grid (Stand-alone) Systems
Off-grid systems operate independently without utility connection.
Architecture: PV array → Charge controller → Battery bank → Off-grid inverter → AC loads
Battery sizing requirement:
Hybrid Systems
Combine grid connection with battery backup:
- AC-coupled or DC-coupled configurations
- Seamless transfer during outages
- Can operate in grid-tied or island mode
Self-consumption vs Export
Self-consumption ratio:
Higher self-consumption = better economics when export rates are low.
Feed-in Tariff (FIT) Fundamentals
A feed-in tariff is a policy mechanism offering long-term contracts to renewable energy producers, typically based on cost of generation.
Three key provisions:
- Guaranteed grid access
- Stable, long-term purchase contracts (10-25 years)
- Cost-based payment rates
Payment Structures
| Model | Description |
|---|---|
| Fixed-price FIT | Set rate regardless of wholesale price |
| Premium FIT | Bonus added to wholesale market price |
| Sliding premium | Premium varies with market conditions |
Net Metering vs Net Billing
Net Energy Metering:
- Bill credits at full retail rate
- Grid acts as "financial storage"
- Meter runs backward during export
Net Billing:
- Export credited at predetermined sell rate
- Usually lower than retail rate
- Separate import/export accounting
UK Smart Export Guarantee (SEG)
Replaced FIT for new installations from January 2020:
- Suppliers with 150,000+ customers must offer SEG
- Rate must be greater than zero
- Requires MCS certification and DNO notification
Economic Analysis
Simple payback period:
Levelized Cost of Energy (LCOE):
- Wikipedia - Distributed Generation https://en.wikipedia.org/wiki/Distributed_generation
Low Voltage Systems
Understanding low voltage (LV) electrical systems as defined by standards. Single-phase vs three-phase supplies, voltage levels, and how domestic properties connect to the distribution network.
- Define low voltage ranges per IEC/BS standards
- Explain single-phase and three-phase supply differences
- Describe the point of common coupling (PCC)
IEC 60038 Voltage Classifications
| Classification | AC Voltage (RMS) | DC Voltage |
|---|---|---|
| Extra-Low Voltage (ELV) | < 50V | < 120V |
| Low Voltage (LV) | 50V – 1000V | 120V – 1500V |
| High Voltage (HV) | > 1000V | > 1500V |
Extra-Low Voltage Categories
- SELV: Separated Extra-Low Voltage (no earth connection, double insulation)
- PELV: Protective Extra-Low Voltage (earth connection permitted)
- FELV: Functional Extra-Low Voltage (requires additional protection measures)
Regional Voltage Differences
| Region | Single-Phase | Three-Phase | Frequency |
|---|---|---|---|
| UK/EU | 230V (±10%) | 400V | 50 Hz |
| USA | 120V | 208V/480V | 60 Hz |
| Japan | 100V/200V | 200V | 50/60 Hz |
Supply Voltage Tolerance
Per EN 50160 and BS EN 50160: $$V_{supply} = V_{nominal} \pm 10%$$
For 230V nominal:
Why LV Matters for Distributed Generation
Most domestic and small commercial generation connects at LV level:
- Simpler protection requirements
- Lower cost interconnection
- G98/G99 regulations apply
230V 50Hz System Configuration
Single-phase supply consists of three conductors:
- Live (L): Carries AC current at 230V RMS to neutral
- Neutral (N): Return path, connected to earth at transformer star point
- Earth (E/PE): Safety conductor for fault current
Voltage Waveform
Where:
- (peak voltage)
- rad/s (at 50Hz)
- Period ms
RMS and Peak Relationship
Power Calculations
Resistive loads (unity power factor):
Reactive loads (with power factor):
Power Triangle
Typical Domestic Capacity
UK domestic supplies typically:
- 60A or 80A main fuse (older properties)
- 100A main fuse (modern properties)
- Maximum demand: ~23kW at 100A
Fundamental Relationships
Three phases displaced by 120° (or 2π/3 radians): $$V_A = V_m\sin(\omega t)$$ $$V_B = V_m\sin(\omega t - 120°)$$ $$V_C = V_m\sin(\omega t + 120°)$$
The √3 Factor
Line voltage to phase voltage relationship: $$V_L = \sqrt{3} \times V_P$$
For EU systems:
This factor arises from the vector sum of two phase voltages 120° apart.
Star (Wye) Connection
- Neutral available for single-phase loads
- Common for distribution systems
Delta Connection
- No neutral conductor
- Common for motors and transformers
Three-Phase Power
Balanced System Property
In a balanced three-phase system: $$I_A + I_B + I_C = 0$$ (vector sum)
This means neutral current is zero for balanced loads.
Why Three-Phase for Larger Installations?
- More power for same conductor size
- Constant instantaneous power (no pulsation)
- More efficient for motors
- Required for generation >3.68kW single-phase
Definition
The Point of Common Coupling (PCC) is the interface point where a distributed energy resource connects to the utility distribution network. It's the electrical location where:
- Power quality measurements are taken
- Interconnection requirements are enforced
- Protection coordination is established
- Multiple customers may share the connection
Why PCC Matters for Distributed Generation
Power Quality Control:
- THD limits measured at PCC (typically <5%)
- Voltage regulation requirements apply at PCC
- Flicker limits (Pst, Plt) assessed at PCC
Voltage Impact:
Protection Coordination at PCC
IEEE 1547 voltage ride-through requirements:
| Condition | Voltage Range | Max Trip Time |
|---|---|---|
| OV2 | V > 1.20 pu | 0.16s |
| OV1 | 1.10 < V ≤ 1.20 pu | 1.0-13.0s |
| UV1 | 0.70 ≤ V < 0.88 pu | 2.0-21.0s |
| UV2 | V < 0.50 pu | 0.16s |
Fault Current at PCC
Total fault current includes utility and DER contributions: $$I_{fault(total)} = I_{fault(utility)} + I_{fault(DER)}$$
Power Flow Direction at PCC
- Positive : Export to grid
- Negative : Import from grid
Short Circuit Ratio at PCC
- SCR > 20: Stiff grid (small voltage impact)
- SCR < 10: Weak grid (significant voltage impact)
- IEC 60038 - Standard Voltages https://en.wikipedia.org/wiki/IEC_60038
Grid Connection & Power Quality
Grid-Tied Inverters
How inverters synchronize with the grid to export power safely. Covers grid-following vs grid-forming inverters, synchronization requirements, and maximum power point tracking (MPPT).
- Explain how grid-tied inverters synchronize with mains
- Differentiate grid-following and grid-forming inverters
- Understand MPPT and its role in solar systems
Grid Synchronization
Grid-tied inverters must precisely match the grid's voltage, frequency, and phase before connecting. Failure to synchronize properly causes large transient currents that can damage equipment and trip protection.
Synchronization Requirements
Three conditions must be met before closing the grid connection:
| Parameter | Tolerance | Typical Grid (UK) |
|---|---|---|
| Voltage magnitude | ±5% | 230V ±10% |
| Frequency | ±0.1 Hz | 50 Hz ±0.5 Hz |
| Phase angle | ±5° | 0° reference |
Phase-Locked Loop (PLL)
The PLL is the core synchronization mechanism. It continuously tracks the grid voltage and generates a reference signal locked to the grid phase:
The PLL uses feedback to minimize phase error:
A PI controller adjusts the internal oscillator frequency until .
Synchronization Sequence
- Monitoring: Measure grid V, f, φ continuously
- Ramping: Adjust inverter output to match grid
- Verification: Confirm all parameters within tolerance
- Connection: Close contactor when synchronized
- Current injection: Begin power export
The synchronization time typically ranges from 20ms to 5 seconds depending on grid stability and inverter design.
Grid-Following Inverter
Grid-following (also called grid-feeding) inverters treat the grid as a stiff voltage source and inject current synchronized to the grid voltage. This is the dominant topology for residential and commercial solar installations.
Operating Principle
The inverter acts as a controlled current source:
Where:
- = current amplitude (controlled by MPPT)
- = grid angular frequency (from PLL)
- = phase angle (typically 0° for unity power factor)
Control Architecture
PV Array → DC-DC (MPPT) → DC Link → DC-AC Inverter → Filter → Grid
↑ ↓
DC voltage Current control
control (PLL-based)
Power Control
Real and reactive power are controlled via current magnitude and phase:
Limitations
- Cannot operate without grid: Requires grid voltage reference
- Stability concerns: High penetration can cause voltage/frequency issues
- No black start capability: Cannot energize a dead grid
Grid-following inverters comply with IEEE 1547 and G98/G99 requirements for anti-islanding - they must disconnect within 2 seconds of grid loss.

Grid-Forming Inverter
Grid-forming inverters create their own voltage and frequency reference, behaving as a voltage source rather than current source. They can operate independently or support weak grids.
Operating Principle
The inverter maintains a controlled output voltage:
Where:
- = voltage amplitude (regulated)
- = internal frequency reference
- = power angle (determines power flow)
Droop Control
Grid-forming inverters use droop characteristics to share load and maintain stability:
Frequency droop (P-f): $$f = f_0 - m_p (P - P_0)$$
Voltage droop (Q-V): $$V = V_0 - n_q (Q - Q_0)$$
Where and are droop coefficients (typically 2-5%).
Comparison Table
| Feature | Grid-Following | Grid-Forming |
|---|---|---|
| Voltage source | No (current source) | Yes |
| Grid required | Yes | No |
| Black start | No | Yes |
| Weak grid support | Limited | Excellent |
| Inertia provision | No | Yes (virtual) |
| Complexity | Lower | Higher |
| Cost | Lower | Higher |
Virtual Synchronous Machine (VSM)
Advanced grid-forming control emulates synchronous generator behaviour:
Where = virtual inertia, = damping coefficient.
This provides synthetic inertia to stabilize grid frequency during disturbances.
Maximum Power Point Tracking (MPPT)
Solar panels have a unique operating point where power output is maximized. MPPT algorithms continuously find and track this point as conditions change.
I-V and P-V Curves
A PV panel's output varies with voltage:
The maximum power point (MPP) occurs where:
Since :
At MPP:
Environmental Effects
| Condition | Effect on | Effect on | Effect on |
|---|---|---|---|
| ↑ Irradiance | Slight ↑ | Proportional ↑ | ↑↑ |
| ↑ Temperature | ↓↓ | Slight ↑ | ↓ |
| Shading | Complex | ↓ | ↓↓ |
Temperature coefficient (typical): for power.
MPPT Algorithms
Perturb & Observe (P&O):
- Simplest, most common algorithm
- Periodically changes and observes
- If , continue same direction
- Oscillates around MPP (1-3% power loss)
Incremental Conductance:
- Compare with
- More accurate tracking
- Better performance under rapidly changing conditions
MPPT efficiency: $$\eta_{MPPT} = \frac{\int P_{actual} , dt}{\int P_{MPP,ideal} , dt} \times 100%$$
Typical MPPT efficiency: 98-99.5% for quality inverters.
- Wikipedia - Solar Inverter https://en.wikipedia.org/wiki/Solar_inverter
Power Quality
Ensuring domestic generation doesn't degrade the grid. Covers harmonics, voltage rise, flicker, and power factor. Why utilities care about power quality and how inverters must comply.
- Define key power quality metrics (THD, voltage deviation, flicker)
- Explain how inverters can inject harmonics
- Understand voltage rise from exporting power
Harmonics & Total Harmonic Distortion
Harmonics are integer multiples of the fundamental frequency (50Hz). Non-linear loads and switching inverters inject harmonic currents that distort the voltage waveform.
Harmonic Series
For a 50Hz fundamental:
| Harmonic | Frequency | Common Sources |
|---|---|---|
| 1st (fundamental) | 50 Hz | Pure sine wave |
| 3rd | 150 Hz | Single-phase rectifiers, LEDs |
| 5th | 250 Hz | VFDs, three-phase rectifiers |
| 7th | 350 Hz | VFDs, UPS systems |
| 11th, 13th | 550, 650 Hz | Large industrial drives |
Fourier Representation
Any periodic waveform can be decomposed:
Where = magnitude of harmonic .
Total Harmonic Distortion (THD)
THD quantifies total harmonic content relative to fundamental:
For current:
Limits and Standards
| Standard | Current THD Limit | Voltage THD Limit |
|---|---|---|
| IEEE 519 | 5% (general) | 5% |
| G98/G99 | 5% | N/A (result of current) |
| EN 50160 | N/A | 8% |
Harmonic Effects
- Overheating: Transformers, cables, motors
- Resonance: With power factor correction capacitors
- Nuisance tripping: RCDs sensitive to high-frequency
- Meter errors: Older meters may read incorrectly
Inverters use output filters (L, LC, or LCL) to limit harmonic injection below regulatory limits.
Voltage Rise from Power Export
When distributed generation exports power, current flows "backwards" through the distribution network impedance, causing voltage to rise at the point of connection.
The Voltage Rise Problem
In a simple radial network:
Substation ──R+jX──┬── Load A
│
└── PV System (exporting)
Voltage at PV connection point:
For power export (P negative by convention, or positive export):
Simplified Approximation
For LV networks where :
Example: 4kW export, 0.5Ω line resistance, 230V: $$\Delta V = \frac{4000 \times 0.5}{230} = 8.7V \approx 3.8%$$
Voltage Limits
| Standard | Steady-State Limit |
|---|---|
| EN 50160 | 230V +10%/-6% (216-253V) |
| G98/G99 | Must not cause voltage >+10% |
| DNO planning | Typically +6% headroom |
Mitigation Strategies
Reactive power control: Absorb Q to offset voltage rise $$Q_{absorb} = -\frac{P \cdot R}{X}$$ (if X significant)
Export limiting: Reduce P when V approaches limit
Volt-VAr mode: Automatic Q adjustment based on voltage $$Q = f(V) \text{ per programmed curve}$$
Network reinforcement: DNO upgrades cables/transformers
Modern inverters implement Volt-VAr and Volt-Watt response curves per G98/G99 requirements.
Power Factor in Grid-Tied Systems
Power factor describes the phase relationship between voltage and current, and the ratio of real power to apparent power.
Power Factor Definition
Where:
- = Real power (W) - does useful work
- = Reactive power (VAr) - energy storage in L/C
- = Apparent power (VA) - total current × voltage
- = Phase angle between V and I
Power Triangle
S (VA)
/|
/ |
/ | Q (VAr)
/φ |
─────┘
P (W)
Displacement vs Distortion Power Factor
Displacement PF (fundamental only): $$PF_{disp} = \cos(\phi_1)$$
Distortion PF (due to harmonics): $$PF_{dist} = \frac{1}{\sqrt{1 + THD_I^2}}$$
True Power Factor: $$PF_{true} = PF_{disp} \times PF_{dist}$$
Grid Code Requirements
| Condition | G98/G99 Requirement |
|---|---|
| Default | Unity PF (1.0) |
| Volt-VAr mode | 0.95 leading to 0.95 lagging |
| DNO request | Adjustable setpoint |
Inverter Capability
Modern inverters can operate across four quadrants:
| Quadrant | P | Q | Mode |
|---|---|---|---|
| I | + | + | Export, supply reactive |
| II | - | + | Import, supply reactive |
| III | - | - | Import, absorb reactive |
| IV | + | - | Export, absorb reactive |
Reactive power capability is limited by inverter VA rating: $$Q_{max} = \sqrt{S_{rated}^2 - P^2}$$
Voltage Flicker
Flicker is rapid, repetitive voltage fluctuation that causes visible light intensity changes. Human eyes are most sensitive to fluctuations around 8-10 Hz.
Causes of Flicker
- Cloud transients: Rapid irradiance changes on PV
- Inverter switching: Connection/disconnection events
- Motor starting: Large inrush currents
- Arc furnaces: Industrial loads with erratic current
Flicker Metrics
Short-term flicker severity ($P_{st}$):
- Measured over 10 minutes
- means threshold of irritability
- Limit: typically
Long-term flicker severity ($P_{lt}$): $$P_{lt} = \sqrt[3]{\frac{1}{12}\sum_{i=1}^{12} P_{st,i}^3}$$
Measured over 2 hours (12 × 10-minute intervals).
Voltage Change Limits
| Standard | Rapid Voltage Change | Flicker Limit |
|---|---|---|
| EN 50160 | ±10% max | |
| G98 | 3% per event | |
| IEEE 1547 | 5% per event | Per utility |
Flicker from PV Systems
Cloud-induced ramp rates can be severe:
Voltage change per power step: $$\Delta V = \frac{\Delta P \cdot R}{V}$$
Mitigation
- Ramp rate limiting: Limit to 10-20%/minute
- Energy storage: Buffer rapid power changes
- Reactive power: Fast Q response to oppose ΔV
- Network stiffness: Lower impedance reduces ΔV
Modern inverters include configurable ramp rate limits and Volt-VAr response to minimize flicker contribution.
- Wikipedia - Electric Power Quality https://en.wikipedia.org/wiki/Electric_power_quality
Export Limiting & Zero Export
Techniques to limit or prevent power export to the grid. Required when grid capacity is constrained or feed-in is not permitted. Covers export limiting, zero export, and dynamic curtailment.
- Explain why export limiting may be required
- Describe zero-export system configurations
- Understand dynamic export limiting
Export Limiting
Export limiting restricts the maximum power that can be exported to the grid, regardless of generation capacity or load conditions.
Why Limit Export?
- Grid capacity constraints: DNO network cannot accept more power
- Connection agreement: G99 approval may specify export limit
- Tariff restrictions: Some feed-in tariffs cap export
- Network charges: Avoid capacity-based export charges
- Self-consumption optimization: Maximize own use
Export Limit Calculation
At the meter point:
Export limiting ensures:
Therefore generation must be curtailed when:
Implementation Methods
Fixed export limit:
- Inverter configured with maximum export (e.g., 3.68kW for G98)
- Simple but may curtail unnecessarily
Dynamic export limiting:
- CT clamp measures actual export
- Real-time curtailment only when needed
- Maximizes generation within limits
G98/G99 Context
| Connection Type | Typical Export Limit |
|---|---|
| G98 (single-phase) | 3.68 kW |
| G98 (three-phase) | 11.04 kW |
| G99 | Per DNO agreement |
Some DNOs offer "flexible connections" with lower limits but faster approval.
Zero Export Systems
Zero export prevents any power flow to the grid, keeping all generated power within the premises. Required in some jurisdictions or where grid export is prohibited.
Use Cases
- No export permitted: Some countries/utilities prohibit export
- Complex metering: Avoid issues with non-bidirectional meters
- Off-grid backup: Systems that can island but normally grid-tied
- Demand charge reduction: Industrial sites avoiding export complications
Control Strategy
The system must satisfy:
Control loop:
- Measure at meter point (CT clamp)
- If (exporting): reduce inverter output
- Target: with small margin
Typical margin: 50-200W to prevent accidental export.
Response Time Requirements
| Scenario | Required Response |
|---|---|
| Load switching off | < 100ms typical |
| Cloud burst (irradiance spike) | < 500ms |
| Acceptable export duration | < 5 seconds |
System Architecture
Grid ──[Meter]──┬── Main Loads
↑ │
CT └── [Inverter] ←── PV Array
│ ↑
└── Signal ────┘
The CT signal feeds directly to the inverter (Modbus, analog, or proprietary).
Limitations
- Wasted energy: Cannot export excess generation
- Battery recommended: Store excess for later use
- Rapid response needed: Fast communication essential
- Partial self-consumption: May not use all available solar

CT Clamp Monitoring
Current transformers (CTs) measure power flow at key points in the system, enabling intelligent control of generation and export.
CT Operating Principle
A CT is a transformer with the measured conductor as primary:
For a clamp-on CT with single primary turn ($N_p = 1$):
Example: 100A:50mA CT (2000:1 ratio)
- Primary current: 100A
- Secondary current: 50mA
- Turns ratio: 2000:1
Measurement Points
Grid ──[CT1]── Main Panel ──[CT2]── Sub-panel
│
[CT3]└── Inverter ── PV
| CT Location | Measures | Purpose |
|---|---|---|
| CT1 (Grid) | Import/export | Export limiting |
| CT2 (Sub-panel) | Critical loads | Backup sizing |
| CT3 (Inverter) | Generation | Monitoring |
Power Calculation
With voltage reference:
For single-phase: $$P = V_{rms} \cdot I_{rms} \cdot PF$$
For three-phase balanced: $$P = \sqrt{3} \cdot V_L \cdot I_L \cdot PF$$
CT Specifications
| Parameter | Typical Values |
|---|---|
| Ratio | 100:5A, 100:50mA, 200:50mA |
| Accuracy class | 0.5, 1.0, 3.0 |
| Burden | 1-5 VA |
| Window size | 10-25mm diameter |
Communication Protocols
| Method | Latency | Common Use |
|---|---|---|
| Analog (0-5V, 4-20mA) | <10ms | Direct inverter input |
| Modbus RTU | 50-200ms | Energy meters |
| Modbus TCP | 20-100ms | Network meters |
| Pulse output | Per-pulse | Simple metering |

Dynamic Curtailment
Dynamic curtailment adjusts generation in real-time based on grid conditions, maximizing output while respecting network constraints.
Curtailment Triggers
| Trigger | Response |
|---|---|
| Voltage high ($V > V_{max}$) | Reduce P and/or absorb Q |
| Frequency high ($f > f_{max}$) | Reduce P |
| Export limit reached | Cap P at limit |
| DNO signal | Reduce per instruction |
Volt-Watt Response
G98/G99 mandates Volt-Watt curtailment:
P(%)
100├────────┐
│ │
│ ╲
20│ ╲
│ ╲────
└──────────────── V(%)
100 106 110
$$P = \begin{cases} P_{max} & V < V_1 \ P_{max} \cdot \frac{V_2 - V}{V_2 - V_1} & V_1 \leq V \leq V_2 \ P_{min} & V > V_2 \end{cases}$$
Typical settings: , ,
Frequency-Watt Response
For high frequency events:
Where = droop coefficient (typically 40%/Hz).
At Hz: Begin reducing power At Hz: Disconnect (protection)
Curtailment Calculation
Energy curtailed over period T:
Annual curtailment percentage: $$\text{Curtailment} = \frac{E_{curtailed}}{E_{potential}} \times 100%$$
Typical values: 0-5% for well-designed systems, up to 20% in constrained networks.
Economic Impact
Lost revenue from curtailment:
Battery storage can capture otherwise-curtailed energy:
- Wikipedia - Feed-in Tariff https://en.wikipedia.org/wiki/Feed-in_tariff
Protection & Compliance
Anti-Islanding Protection
Preventing dangerous situations when the grid goes down. If generation continues during an outage, it creates an "island" that endangers utility workers. Covers detection methods and protection requirements.
- Explain the islanding hazard
- Describe passive and active anti-islanding methods
- Understand loss-of-mains protection requirements
Islanding
Islanding occurs when a distributed generator continues to power a section of the network after the grid supply has been disconnected. This creates a dangerous "island" of live conductors.
The Hazard
[Grid] ──X── [Local Network] ←── [DG]
↑ ↓
Open Still energized!
breaker
Dangers:
- Electrocution: Workers assume lines are dead after isolation
- Equipment damage: Voltage/frequency may drift outside limits
- Out-of-phase reconnection: When grid returns, severe transients
- Fire risk: Uncontrolled energy source
Islanding Conditions
For an island to persist, generation must match load:
The probability of exact balance is low, but the consequences are severe enough to require active prevention.
Non-Detection Zone (NDZ)
The NDZ defines the power mismatch range where islanding may go undetected:
If AND , detection may fail.
Regulatory Requirements
| Standard | Disconnection Time |
|---|---|
| IEEE 1547 | < 2 seconds |
| G98/G99 | < 0.5 seconds (LoM) |
| VDE-AR-N 4105 | < 0.2 seconds |
All grid-tied inverters must include anti-islanding protection as a fundamental safety feature.
Loss of Mains (LoM) Protection
Loss of Mains detection identifies when the grid connection has been lost, triggering immediate disconnection of the distributed generator.
Detection Philosophy
The inverter must detect grid loss even when:
- Local generation exactly matches local load
- Voltage and frequency remain within normal bounds
- No obvious transient occurs
LoM Detection Methods
| Method | Type | Detection Time | Reliability |
|---|---|---|---|
| Under/over voltage | Passive | Fast | Moderate |
| Under/over frequency | Passive | Fast | Moderate |
| Rate of change of frequency (RoCoF) | Passive | Very fast | Good |
| Vector shift | Passive | Very fast | Good |
| Impedance measurement | Active | Moderate | Excellent |
| Frequency shift | Active | Moderate | Excellent |
G98/G99 Requirements
UK installations must implement:
- Under-voltage: Trip if for > 0.5s
- Over-voltage: Trip if for > 1.0s
- Under-frequency: Trip if Hz for > 0.5s
- Over-frequency: Trip if Hz for > 0.5s
- RoCoF: Trip if Hz/s (adjustable)
RoCoF Calculation
Measured over 100-500ms window. Normal grid RoCoF: < 0.1 Hz/s. Islanding RoCoF: typically > 0.5 Hz/s.
Reconnection Requirements
After LoM trip, reconnection only permitted when:
- Voltage within ±10% for > 60 seconds
- Frequency within ±0.5 Hz for > 60 seconds
- Minimum delay: 20 seconds (G98) to 3 minutes (some utilities)
Passive Anti-Islanding Detection
Passive methods monitor grid parameters without injecting any disturbance. They rely on natural changes when the grid disconnects.
Under/Over Voltage Protection (U/OVP)
Monitors RMS voltage against thresholds:
| Stage | Threshold (G98/G99) | Trip Time |
|---|---|---|
| UV2 | < 0.80 × Vnom | < 0.5s |
| UV1 | < 0.87 × Vnom | < 2.5s |
| OV1 | > 1.10 × Vnom | < 1.0s |
| OV2 | > 1.14 × Vnom | < 0.5s |
Under/Over Frequency Protection (U/OFP)
Monitors grid frequency:
| Stage | Threshold | Trip Time |
|---|---|---|
| UF2 | < 47.0 Hz | < 0.5s |
| UF1 | < 47.5 Hz | < 20s |
| OF1 | > 52.0 Hz | < 0.5s |
Rate of Change of Frequency (RoCoF)
Detects rapid frequency excursions:
Typical setting: 0.5 - 1.0 Hz/s over 500ms window.
Advantages: Fast detection, simple implementation Disadvantages: May trip on genuine grid events
Vector Shift (Phase Jump)
Detects sudden phase angle changes:
Where = one cycle (20ms at 50Hz).
Trip if to (adjustable).
Limitations of Passive Methods
All passive methods have a Non-Detection Zone where islanding can persist:
- Balanced load/generation
- High-Q resonant loads
- Multiple inverters on same island
This is why active methods are also required.
Active Anti-Islanding Detection
Active methods deliberately inject small disturbances and measure the grid's response. A stiff grid resists change; an island drifts.
Principle
Inject disturbance → Measure response → Grid present?
↓
Minimal change ←─── Yes (stiff grid)
Large drift ←───── No (island)
Impedance Measurement
Inject a small current at non-fundamental frequency and measure resulting voltage:
| Condition | Impedance |
|---|---|
| Grid connected | Low (< 1Ω typical) |
| Islanded | High (load impedance) |
Detection threshold: Typically 2-5× normal impedance.
Active Frequency Drift (AFD)
Also called Sandia Frequency Shift (SFS):
The inverter deliberately pushes frequency slightly:
Where = positive feedback gain (typically 0.01-0.05).
- Grid connected: Grid holds frequency stable
- Islanded: Frequency drifts until U/OFP trips
Slip Mode Frequency Shift (SMS)
Phase is advanced when frequency exceeds nominal:
This accelerates frequency deviation during islanding.
Reactive Power Variation
Periodically vary Q output:
Monitor voltage response at .
| Condition | Voltage Response |
|---|---|
| Grid connected | Negligible |
| Islanded | Proportional to Q |
Comparison
| Method | NDZ | Power Quality Impact | Complexity |
|---|---|---|---|
| AFD/SFS | Very small | Low THD increase | Medium |
| SMS | Very small | Low | Medium |
| Impedance | None | Slight distortion | High |
| Q variation | Small | Minor flicker | Medium |
Modern inverters combine multiple methods for robust detection across all scenarios.
- Wikipedia - Islanding https://en.wikipedia.org/wiki/Islanding
Standards & Regulations
UK and international standards for connecting generation to the grid. G98 for small installations, G99 for larger ones. DNO notification and approval processes.
- Differentiate G98 and G99 requirements
- Understand DNO notification process
- Identify key compliance requirements
G98: Small-Scale Generation
G98 (formerly G83) is the UK standard for connecting small-scale embedded generators to the low voltage distribution network. It provides a simplified "fit and notify" process for domestic installations.
Scope
| Parameter | G98 Limit |
|---|---|
| Single-phase | ≤ 3.68 kW per phase |
| Three-phase | ≤ 11.04 kW total |
| Voltage | LV (≤ 400V) |
| Connection | Single premises |
The 3.68 kW limit derives from 16A × 230V = 3,680W.
Key Requirements
Equipment:
- Type-tested inverter to G98
- Protection settings factory-configured
- Installer cannot modify protection
Protection Settings (fixed):
| Function | Setting | Time |
|---|---|---|
| Over-voltage stage 1 | 264V (+14.8%) | 1.0s |
| Over-voltage stage 2 | 253V (+10%) | Instantaneous |
| Under-voltage stage 1 | 207V (-10%) | 2.5s |
| Under-voltage stage 2 | 195.5V (-15%) | 0.5s |
| Over-frequency | 52 Hz | 0.5s |
| Under-frequency | 47.5 Hz | 20s |
| Loss of mains | Per type test | 0.5s |
Notification Process
- Install: Complete installation per BS 7671
- Notify: Submit notification to DNO within 28 days
- Commission: Inverter self-tests on first power-up
- Confirm: DNO may inspect (rarely for G98)
Notification is via DNO portals or the national MCS portal.
No Approval Required
Unlike G99, G98 installations do not require prior DNO approval. The installer simply notifies after completion.

G99: Larger-Scale Generation
G99 (formerly G59) covers larger embedded generation systems requiring DNO assessment and approval before connection.
Scope
| Type | Capacity | Process |
|---|---|---|
| Type A | > 3.68 kW to 50 kW | Notification + approval |
| Type B | 50 kW to 1 MW | Full application |
| Type C | 1 MW to 10 MW | Detailed study |
| Type D | > 10 MW | Bespoke connection |
Application Process
Application → DNO Assessment → Offer → Acceptance → Install → Commission
↓ ↓ ↓ ↓ ↓ ↓
4 weeks 4-12 weeks 28 days Sign + pay Build Witness test
Assessment includes:
- Fault level contribution
- Voltage rise calculation
- Thermal capacity check
- Protection coordination
Technical Requirements
Protection (Type A example):
| Function | Default | Range |
|---|---|---|
| OV1 | 262.2V | 253-270V |
| UV1 | 216.2V | 195.5-216.2V |
| OF1 | 52 Hz | 50.5-52 Hz |
| UF1 | 47.5 Hz | 47-47.5 Hz |
| RoCoF | 1.0 Hz/s | 0.125-1.0 Hz/s |
Settings may be adjusted by DNO based on local network.
Additional Features (vs G98)
- Remote disconnection: DNO can disable generation
- Power quality monitoring: Continuous logging
- Witness testing: DNO attends commissioning
- Interface protection: Separate relay may be required
Export Limits
G99 applications often receive:
- Firm connection: Full export capacity guaranteed
- Flexible connection: Export limited during constraints
- Timed connection: Export only at certain times
DNO Notification Process
Distribution Network Operators (DNOs) manage the electricity network and must be informed of all generation connections.
UK DNOs
| Region | DNO |
|---|---|
| South/South East | UK Power Networks (UKPN) |
| North West | Electricity North West (ENWL) |
| Midlands | Western Power Distribution (WPD) |
| North East/Yorkshire | Northern Powergrid |
| Scotland South | SP Energy Networks |
| Scotland North | SSE Networks |
G98 Notification (Simple)
Information required:
- Site address and MPAN
- Installer details (MCS certified)
- Equipment make/model
- Installed capacity (kW)
- Single/three-phase
- Commissioning date
Timeline:
- Notify within 28 days of commissioning
- No response required (deemed acceptance)
G99 Application (Detailed)
Stage 1 - Budget Estimate (optional):
- Basic site info
- Approximate capacity
- Response: ~2 weeks
Stage 2 - Full Application:
- Detailed design
- Protection settings
- Single-line diagram
- Site plans
- Response: 45-65 working days
Application Fees
| Capacity | Typical Fee |
|---|---|
| G98 | Free |
| G99 Type A (< 50 kW) | £0 - £300 |
| G99 Type B (< 1 MW) | £500 - £2,000 |
| G99 Type C/D | £2,000+ |
Additional costs for network reinforcement may apply.
Common Issues
- Voltage rise: Export may be limited
- Fault level: May require current-limiting inverter
- Protection coordination: Settings adjustment needed
- Reverse power flow: Transformer issues

Type Testing & Certification
Grid-connected equipment must be independently tested and certified before sale in the UK and EU.
Type Test Purpose
Demonstrates that a product design meets:
- Safety requirements
- Performance standards
- Grid code compliance
- EMC regulations
Individual units are not tested; the type (design) is certified.
G98/G99 Type Testing
Inverters must pass tests including:
| Test | Requirement |
|---|---|
| Anti-islanding | Detect island < 0.5s |
| Over/under voltage | Trip within specified times |
| Over/under frequency | Trip within specified times |
| RoCoF | Detect and respond correctly |
| Reconnection | Correct delay and ramping |
| Power quality | THD < 5%, PF adjustable |
| EMC | EN 61000-6-1/2/3/4 |
Test Laboratories
UK-recognised test houses:
- DNV GL (KEMA)
- TÜV Rheinland/SÜD
- CSA Group
- Intertek
- SGS
Testing typically costs £10,000 - £50,000 per product variant.
Certification Marks
| Mark | Meaning |
|---|---|
| CE/UKCA | EU/UK safety compliance |
| G98 | UK small-scale connection |
| G99 | UK larger-scale connection |
| VDE-AR-N 4105 | German grid code |
| UL 1741 | US grid code |
Product Documentation
Compliant inverters include:
- Type test certificate (reference number)
- G98/G99 compliance declaration
- Protection settings table
- Installation manual with grid code section
Installer responsibility: Verify equipment has valid type test certificate before installation.
G100 (Power Limiting)
New standard for power limiting devices:
- Tested separately from inverter
- Ensures export limits are enforced
- Required for flexible connections
- RENEW-ABLE SOLUTIONS - What is G98, G99 & G100? All explained here https://www.renew-able.co.uk/what-is-g98-g99-g100-all-explained-here/
Earthing & Safety optional
Proper earthing for domestic generation systems. Covers TN-C-S, TN-S, and TT earthing arrangements, RCD protection, and DC safety for solar PV systems.
- Identify UK earthing arrangements
- Explain RCD and RCBO protection
- Understand DC isolation requirements for PV
Earthing Arrangements
The earthing system determines how fault currents return to source and how shock protection operates. UK domestic installations use three main arrangements.
TN-C-S (PME - Protective Multiple Earthing)
Most common in UK. The neutral and earth are combined in the supply cable, then separated at the premises.
Substation Service Consumer Unit
│ │ │
N ──┼──────────────────┼──────────────────┼── N
│ PEN conductor │ │
E ──┴──────────────────┼──────────────────┼── E
↓ │
Separated here Main earth
Characteristics:
- Low impedance earth path
- Earth potential can rise during faults
- Restrictions on earthing in some zones
PV considerations:
- Additional earth electrode may be required
- PME earthing restrictions for outdoor equipment
TN-S (Separate Earth)
Separate earth conductor from substation. Less common but considered superior.
Substation Service Consumer Unit
│ │ │
N ──┼──────────────────┼──────────────────┼── N
│ │ │
E ──┼──────────────────┼──────────────────┼── E
│ │ │
═╧═ Cable Main earth
Earth sheath
s```
**Characteristics**:
- True earth reference
- No neutral/earth rise issues
- Often found in older installations
### TT (Terra-Terra)
Earth electrode at premises; no earth from supply. Common in rural areas.
Substation Service Consumer Unit │ │ │ N ──┼──────────────────┼──────────────────┼── N │ │ │ ═╧═ None ═╧═ ← Local electrode Earth Premises earth
**Characteristics**:
- Higher earth impedance (< 200Ω required)
- RCD protection mandatory
- Suitable for PV installations
### Comparison Table
| Arrangement | Zs Typical | RCD Required? | PV Suitability |
|-------------|------------|---------------|----------------|
| TN-C-S (PME) | 0.35Ω | Recommended | Restrictions apply |
| TN-S | 0.8Ω | Recommended | Good |
| TT | 20-200Ω | Mandatory | Excellent |

RCD Protection
Residual Current Devices detect earth leakage and disconnect before dangerous shock or fire can occur. Essential for PV installations.
Operating Principle
An RCD sums the currents in live and neutral:
Under normal conditions:
If current leaks to earth:
The RCD trips when (rated sensitivity).
RCD Types
| Type | Detects | Application |
|---|---|---|
| AC | Sinusoidal AC only | Basic circuits |
| A | AC + pulsating DC | Most equipment |
| F | AC + high frequency | VFDs, inverters |
| B | AC + smooth DC | PV, EV chargers |
PV systems require Type B or Type A + upstream detection due to potential DC fault currents from inverter.
Sensitivity Ratings
| Rating | Trip Current | Purpose |
|---|---|---|
| 30mA | 15-30mA | Personal protection |
| 100mA | 50-100mA | Fire protection |
| 300mA | 150-300mA | Main switch backup |
For shock protection, trip time at 5× :
- 30mA RCD: < 40ms at 150mA
- Limits energy:
RCBO (RCD + MCB)
Combined device provides:
- Residual current protection (earth leakage)
- Overcurrent protection (overload, short circuit)
PV-Specific Requirements
BS 7671 requires:
- RCD on AC circuits supplied by inverter
- Type B if inverter doesn't have DC fault detection
- Type A acceptable if inverter has internal DC detection
Nuisance tripping: High-frequency leakage from long DC cables can cause unwanted trips. Solutions:
- Type B RCD (less sensitive to HF)
- Ensure DC cable capacitance is low
- Quality inverter with internal filtering
DC Isolation for PV Systems
Solar PV systems present unique DC hazards. Proper isolation ensures safe maintenance and emergency disconnection.
The DC Hazard
PV panels produce DC voltage whenever illuminated:
Example: 10 panels × 45V = 450V DC (lethal!)
Unlike AC, DC arcs don't self-extinguish at zero-crossing. DC arc temperatures exceed 3,000°C.
Isolation Requirements
BS 7671 and EN 62446 require:
| Location | Isolation Device |
|---|---|
| Array (roof) | DC isolator at array |
| String entry | Fused disconnect (if multiple strings) |
| Inverter input | DC isolator (often integral) |
| Inverter output | AC isolator |
DC Isolator Ratings
Must be rated for PV service:
| Parameter | Typical Requirement |
|---|---|
| Voltage | 1.2 × at -10°C |
| Current | 1.25 × |
| Utilisation category | DC-PV1 or DC-PV2 |
| IP rating | IP65+ for outdoor |
Warning: Standard AC isolators will fail catastrophically on DC!
Firefighter Safety Switch
Rapid shutdown requirement (increasing adoption):
- Reduces array voltage to < 30V within seconds
- Triggered by AC disconnect
- Module-level or string-level shutdown
Isolation Sequence
Safe shutdown procedure:
- Switch off AC isolator (stops current flow)
- Wait 5 minutes (capacitor discharge)
- Switch off DC isolator
- Verify with multimeter before touching
Never disconnect DC under load! Open-circuit voltage always present when illuminated.
Testing
| Test | Method | Requirement |
|---|---|---|
| Insulation | 500V DC megger | > 1MΩ per string |
| Polarity | Multimeter | Correct at all points |
| Multimeter | Within ±5% of expected | |
| Clamp meter | Within ±10% of expected |

Arc Fault Detection
DC arc faults in PV systems cause fires. Arc Fault Circuit Interrupters (AFCIs) detect and interrupt arcs before damage occurs.
Arc Fault Causes
- Loose connections: Corroded or poorly torqued terminals
- Damaged cables: Rodent damage, UV degradation, mechanical
- Connector faults: Mismatched or damaged MC4 connectors
- Water ingress: Tracking across wet insulation
Series vs Parallel Arcs
Series arc (in current path):
PV → ─╱╲─ → Load
arc
- Current limited by load/PV characteristics
- Harder to detect (current may be normal)
- Most common type
Parallel arc (line to line/ground):
PV+ ─────┐
⚡ arc
PV- ─────┘
- High current, easier to detect
- Requires low impedance path
- Often causes immediate failure
Arc Signatures
DC arcs have characteristic signatures:
| Parameter | Normal | Arc Fault |
|---|---|---|
| Noise spectrum | Low HF | Broadband noise 1-500kHz |
| Current pattern | Smooth | Chaotic fluctuation |
| Voltage | Stable | Unstable dips |
AFCI detection algorithm:
Trip if exceeds threshold for sustained period.
AFCI Implementation
| Level | Device Location | Coverage |
|---|---|---|
| String | At inverter input | Entire string |
| Module | At each module | Individual module |
| Inverter | Integrated | Entire array |
US NEC 690.11 requires AFCI for all new PV installations. UK currently recommends but doesn't mandate.
Limitations
- False positives: Inverter switching, poor connections
- Nuisance trips: During commissioning, testing
- Cost: Adds £50-200 per string
- Compatibility: Must work with specific inverter
Best Practice
Prevent arcs through good installation:
- Torque all connections to specification
- Use matched MC4 connectors only
- Protect cables from mechanical damage
- Regular thermographic inspection
- IET - Earthing Arrangements https://electrical.theiet.org/
System Design
System Sizing
Designing a domestic generation system to meet energy needs. Covers load analysis, generation estimation, and storage sizing. Balance between self-consumption, export, and cost.
- Perform basic load analysis
- Size a PV system for a domestic property
- Determine appropriate battery storage capacity
System Sizing Methodology
Proper sizing balances generation, consumption, storage, and economics. Oversizing wastes money; undersizing misses potential.
Design Objectives
Different goals lead to different designs:
| Objective | Sizing Approach |
|---|---|
| Maximum self-consumption | Match generation to daytime load |
| Maximum export income | Largest affordable array |
| Energy independence | Size for worst month + storage |
| Bill reduction | Target 80-100% of annual consumption |
| Carbon reduction | Maximize renewable generation |
Sizing Process
1. Load Analysis → Annual kWh, daily profile, seasonal variation
↓
2. Site Assessment → Roof area, orientation, shading
↓
3. Generation Estimate → Expected yield (kWh/kWp/year)
↓
4. System Size → Match objectives and constraints
↓
5. Storage Sizing → If battery included
↓
6. Economic Analysis → Payback, ROI, NPV
Key Ratios
Self-consumption ratio (SCR): $$SCR = \frac{E_{consumed,direct}}{E_{generated}} \times 100%$$
Typical without battery: 25-40% With battery: 50-80%
Self-sufficiency ratio (SSR): $$SSR = \frac{E_{from,PV}}{E_{total,consumed}} \times 100%$$
Also called "autarky" - how much of your consumption comes from your system.
Specific yield: $$Y_{specific} = \frac{E_{annual}}{P_{rated}} \text{ kWh/kWp/year}$$
UK range: 800-1,000 kWh/kWp/year depending on location and orientation.
Rule of Thumb Sizing
| Annual Consumption | Suggested PV Size | Expected Yield |
|---|---|---|
| 2,500 kWh | 2.5-3 kWp | 2,200-2,700 kWh |
| 4,000 kWh | 4-5 kWp | 3,500-4,500 kWh |
| 6,000 kWh | 5-6 kWp | 4,400-5,400 kWh |
Oversizing by 20-30% is common to account for:
- System losses
- Future consumption growth (EV, heat pump)
- Degradation over lifetime
Load Analysis
Understanding consumption patterns is essential for optimal system design. Analysis reveals how much energy is used, when, and by what.
Data Sources
| Source | Resolution | Availability |
|---|---|---|
| Annual bills | Monthly | Universal |
| Smart meter | 30-minute | Most UK homes |
| Energy monitor | Real-time | If installed |
| Sub-metering | Per circuit | Detailed installs |
Key Metrics
Annual consumption: $$E_{annual} = \sum_{i=1}^{12} E_{month,i} \text{ kWh}$$
UK domestic average: ~2,900 kWh (without electric heating)
Daily average: $$E_{daily,avg} = \frac{E_{annual}}{365} \text{ kWh/day}$$
Peak demand: $$P_{peak} = \max(P(t)) \text{ kW}$$
Typical domestic: 5-10 kW during cooking/kettle.
Load Profile Analysis
Half-hourly smart meter data reveals patterns:
Power (kW)
3│ ┌─┐
│ │ │ ┌───┐
2│ ┌─┐ │ │ │ │
│ │ │ │ │ ┌──┤ │
1│────┤ ├─┤ ├──┤ │ │
│ │ │ │ │ │ │ │
0└────┴─┴─┴─┴──┴──┴───┴────
0 6 12 18 24 hour
Morning Evening
peak peak
Baseload: Always-on consumption (fridge, standby, router)
- Typical: 100-300W continuous
- Annual: kWh
Seasonal Variation
| Season | Factor vs Average | Notes |
|---|---|---|
| Winter | 1.2-1.5× | Heating, lighting |
| Summer | 0.7-0.9× | Less heating, more daylight |
| Spring/Autumn | 1.0× | Baseline |
Load Categories
| Category | Typical % | Flexibility |
|---|---|---|
| Baseload | 25-35% | None |
| Heating/cooling | 20-40% | Some (thermal mass) |
| Hot water | 10-20% | High (tank storage) |
| Cooking | 5-10% | Low |
| Appliances | 15-25% | Medium |
| EV charging | 0-30% | Very high |
Load shifting potential: Moving flexible loads to solar generation hours increases self-consumption significantly.

Generation Estimation
Predicting annual yield requires understanding irradiance data, system losses, and site-specific factors.
Solar Resource
UK annual irradiation varies by location:
| Region | Irradiation (kWh/m²/year) |
|---|---|
| South Coast | 1,100-1,200 |
| Midlands | 1,000-1,100 |
| Scotland | 900-1,000 |
| Northern Ireland | 950-1,050 |
Orientation & Tilt Effects
Optimal UK orientation: South-facing, 30-40° tilt.
| Orientation | Tilt | Yield vs Optimal |
|---|---|---|
| South | 35° | 100% |
| South | 0° (flat) | 89% |
| South | 90° (vertical) | 70% |
| SE/SW | 35° | 96% |
| East/West | 35° | 85% |
| North | 35° | 55% |
Dual-pitch (East-West): Common on modern roofs. Total yield ~85% but flatter generation curve improves self-consumption.
Generation Formula
Where:
- = Array rated power (kWp)
- = Plane-of-array irradiation (kWh/m²/year)
- = Performance Ratio (typically 0.75-0.85)
Performance Ratio Components
| Loss Factor | Typical Value | Notes |
|---|---|---|
| Temperature | 0.90-0.95 | Higher in summer |
| Soiling | 0.97-0.99 | UK rain helps |
| Mismatch | 0.97-0.99 | String configuration |
| Wiring DC | 0.98-0.99 | Cable sizing |
| Inverter | 0.96-0.98 | Quality dependent |
| Wiring AC | 0.99 | Short runs |
Combined PR: typically 0.75-0.85 for well-designed systems.
Monthly Distribution
UK generation varies dramatically by month:
| Month | % of Annual Yield |
|---|---|
| December | 2-3% |
| January | 2-3% |
| June | 12-14% |
| July | 12-14% |
Winter months produce ~10× less than summer months.
Shading Analysis
Even small shadows cause disproportionate losses:
One shaded cell can limit entire string current. Tools for analysis:
- Sun path diagrams
- 3D modelling (PVsyst, SketchUp)
- On-site horizon measurement

Battery Storage Sizing
Batteries store excess generation for later use, increasing self-consumption and providing backup capability.
Sizing Objectives
| Goal | Sizing Approach |
|---|---|
| Maximise self-consumption | 1-day excess generation |
| Time-of-use arbitrage | Peak shaving capacity |
| Backup power | Critical load × duration |
| Grid independence | Multi-day autonomy |
Self-Consumption Sizing
Estimate daily excess generation:
Practical rule: Battery capacity = 50-100% of daily excess.
Example:
- 4 kWp system: ~11 kWh/day (summer average)
- Daytime consumption: 4 kWh
- Excess: 7 kWh
- Suggested battery: 5-7 kWh usable
Usable Capacity
Manufacturers quote total capacity; usable is less:
| Chemistry | Typical DoD | 10 kWh Total → Usable |
|---|---|---|
| Li-ion NMC | 90-95% | 9.0-9.5 kWh |
| LFP (LiFePO4) | 95-100% | 9.5-10 kWh |
| Lead-acid | 50% | 5 kWh |
Cycle Life Consideration
Deeper cycles = fewer total cycles:
| DoD per Cycle | Typical Cycle Life |
|---|---|
| 80% | 3,000-5,000 |
| 50% | 5,000-8,000 |
| 30% | 8,000-12,000 |
Annual cycles: ~250-350 (once daily average).
Expected lifetime: 10-15 years for quality lithium systems.
Power Rating
Battery power rating limits charge/discharge rate:
For 10 kWh battery at 0.5C: 5 kW max power.
Must cover:
- Peak export (to capture all excess)
- Peak consumption (to avoid grid import)
- Backup loads (if required)
Economic Sizing
Diminishing returns with larger batteries:
| Battery Size | Self-Consumption | Marginal Benefit |
|---|---|---|
| 0 kWh | 30% | - |
| 5 kWh | 55% | +25% |
| 10 kWh | 70% | +15% |
| 15 kWh | 78% | +8% |
| 20 kWh | 82% | +4% |
Sweet spot: Usually 1-1.5 × daily excess.
Backup Considerations
For backup power sizing:
Example: 1 kW critical loads × 4 hours × 1.05 = 4.2 kWh minimum.
- Energy Saving Trust - Solar PV https://energysavingtrust.org.uk/advice/solar-panels/
Metering & Monitoring
Measuring and monitoring system performance. Smart meters, generation meters, and monitoring platforms. Understanding performance metrics and identifying issues.
- Understand metering arrangements for grid-tied systems
- Select appropriate monitoring solutions
- Calculate and interpret performance metrics
Smart Meters
Smart meters enable accurate billing, export payments, and detailed consumption data essential for optimizing solar + storage systems.
UK Smart Meter Rollout
Two generations deployed:
| Generation | Communication | Status |
|---|---|---|
| SMETS1 | Proprietary | Legacy (some issues) |
| SMETS2 | Standardised DCC | Current standard |
SMETS2 meters communicate via the Data Communications Company (DCC) network and work with any supplier.
Meter Configuration for Solar
Import/Export metering:
Grid ←──[Smart Meter]──→ Consumer Unit ←── Inverter ←── PV
↓ ↓
Measures: Generation
- Import (+) meter
- Export (-) (separate)
The smart meter records:
- Import: Energy drawn from grid (you pay)
- Export: Energy sent to grid (you're paid)
Meter Modes
| Mode | Export Measurement | Payment Basis |
|---|---|---|
| Net metering | Bidirectional actual | Net consumption |
| Gross metering | Separate meters | Total generation |
| Deemed export | Estimated (50%) | Fixed percentage |
| Actual export | Smart meter reads | Metered export |
SEG (Smart Export Guarantee) requires actual export metering via smart meter or separate export meter.
Half-Hourly Data
Smart meters record consumption in 30-minute intervals:
This data enables:
- Accurate time-of-use billing
- Load profile analysis
- Self-consumption calculation
- System optimization
Data Access
| Method | Update Frequency | Detail Level |
|---|---|---|
| In-home display (IHD) | Real-time | Instantaneous |
| Supplier app | Daily | 30-minute |
| Consumer Access Device | Real-time | 10-second |
| DCC Other User | On request | Full history |
Third-party apps (Loop, Hildebrand) can access data via CAD or DCC.
Generation Metering
Separate generation meter required for:
- Feed-in Tariff (FIT) legacy payments
- Renewable Energy Guarantees of Origin (REGOs)
- Some export tariffs
Must be MCS-certified meter, typically MID-approved.

Monitoring Systems
Monitoring systems track generation, consumption, and system health in real-time, enabling optimization and fault detection.
Monitoring Levels
| Level | Data Source | Visibility |
|---|---|---|
| Inverter | Built-in sensors | Generation only |
| Meter-level | CT clamps + meter | Full energy flows |
| Circuit-level | Individual CTs | Per-circuit detail |
| Module-level | Optimizers/microinverters | Per-panel data |
System Architecture
Cloud Platform ←── Internet ←── Gateway/Logger
↓ ↑
Mobile App ┌────┴────┐
Web Portal │ │
Inverter Meter
↑ ↑
PV Grid CT
Communication Protocols
| Protocol | Use Case | Typical Latency |
|---|---|---|
| Modbus RTU | Inverter → logger | < 1s |
| Modbus TCP | LAN devices | < 1s |
| WiFi | Logger → cloud | 1-5 min upload |
| Cellular | Remote sites | 1-5 min upload |
| RS485 | Daisy-chain devices | < 1s |
Monitoring Parameters
Generation metrics:
- Instantaneous power (W)
- Daily/monthly/annual yield (kWh)
- DC voltage and current per string
- AC voltage, current, frequency
Consumption metrics:
- Grid import/export (W, kWh)
- Self-consumption (W, kWh)
- Load breakdown (if circuit monitoring)
System health:
- Inverter status and alarms
- String performance comparison
- Temperature (ambient, module)
- Communication status
Popular Platforms
| Platform | Compatible Inverters | Features |
|---|---|---|
| SolarEdge | SolarEdge | Module-level, optimizer |
| Enphase | Enphase | Microinverter, per-panel |
| Fronius Solar.web | Fronius | Good analytics |
| SMA Sunny Portal | SMA | Comprehensive |
| GivEnergy | GivEnergy | Battery focus, open API |
| Solis Cloud | Solis | Budget-friendly |
Third-Party Aggregators
Combine data from multiple sources:
- pvoutput.org: Free, community comparison
- Solar Analytics: Advanced diagnostics
- Home Assistant: DIY integration, local control
Data Logging
Systematic data collection enables performance analysis, fault detection, and long-term yield verification.
Logging Resolution
| Resolution | Storage/Year | Use Case |
|---|---|---|
| 1 second | ~1 GB | Transient analysis |
| 1 minute | ~50 MB | Detailed monitoring |
| 5 minute | ~10 MB | Standard monitoring |
| 15 minute | ~3 MB | Long-term storage |
| 30 minute | ~1.5 MB | Billing reconciliation |
Typical systems log at 5-minute intervals with daily upload.
Essential Data Points
Minimum logging set:
- Timestamp (UTC or local with timezone)
- AC power output (W)
- Daily yield (kWh)
- Grid import/export (kWh)
- Inverter status code
Enhanced logging:
- DC voltage per string
- DC current per string
- AC voltage, current, frequency
- Power factor
- Temperature (inverter, ambient)
- Irradiance (if sensor installed)
Data Quality
Common issues and solutions:
| Issue | Cause | Solution |
|---|---|---|
| Gaps | Communication failure | Local buffer, retry |
| Spikes | Sensor glitch | Filtering, validation |
| Drift | Clock skew | NTP sync |
| Missing days | Logger offline | Redundant logging |
Data validation checks: $$P_{max,expected} = G \times A \times \eta$$ Flag if
Storage Options
| Location | Pros | Cons |
|---|---|---|
| Cloud | Accessible anywhere, backed up | Requires internet, ongoing cost |
| Local SD card | No internet needed, private | Manual download, card failure |
| Local NAS/server | Full control, high capacity | Setup complexity |
| Hybrid | Best of both | More complex |
Data Export Formats
| Format | Use |
|---|---|
| CSV | Universal, spreadsheet analysis |
| JSON | API integration, programming |
| XML | Legacy systems |
| Modbus registers | Real-time integration |
Retention Requirements
| Purpose | Recommended Retention |
|---|---|
| Billing verification | 2 years |
| Warranty claims | System lifetime |
| Performance analysis | 5+ years |
| Research/benchmarking | Indefinite |

Performance Metrics
Key performance indicators (KPIs) quantify system health, enabling comparison against expectations and identification of issues.
Specific Yield
Energy produced per unit capacity:
Also called "final yield" or "capacity factor equivalent hours".
| Period | Good UK Performance |
|---|---|
| Daily (summer) | 4-5 kWh/kWp |
| Daily (winter) | 0.5-1 kWh/kWp |
| Annual | 850-1,000 kWh/kWp |
Performance Ratio (PR)
Actual vs theoretical output:
Where = plane-of-array irradiation.
| PR Value | Interpretation |
|---|---|
| > 0.85 | Excellent |
| 0.75-0.85 | Good |
| 0.65-0.75 | Fair (investigate) |
| < 0.65 | Poor (fault likely) |
Temperature-corrected PR: $$PR_{corr} = PR \times \frac{1}{1 + \gamma (T_{cell} - T_{STC})}$$
Where ≈ -0.004/°C for crystalline silicon.
Capacity Factor
Utilisation of rated capacity:
For annual period:
UK PV typical: 10-12% (vs 25-30% in sunny climates).
Self-Consumption Metrics
Self-consumption ratio: $$SCR = \frac{E_{self-consumed}}{E_{generated}} \times 100%$$
Self-sufficiency ratio: $$SSR = \frac{E_{from-PV}}{E_{total-demand}} \times 100%$$
| System Type | Typical SCR | Typical SSR |
|---|---|---|
| PV only | 25-40% | 20-35% |
| PV + battery | 60-80% | 50-70% |
| PV + battery + smart loads | 70-90% | 60-80% |
Degradation Tracking
PV modules degrade over time:
Where = annual degradation rate (typically 0.3-0.7%/year).
Detecting abnormal degradation:
- Compare year-on-year performance
- Temperature-correct for fair comparison
- Flag if degradation > 1%/year
Fault Detection Metrics
| Metric | Normal Range | Fault Indication |
|---|---|---|
| String voltage ratio | 0.95-1.05 | String mismatch |
| PR sudden drop | < 5%/month | Inverter/shading issue |
| Yield vs neighbours | ±10% | System-specific problem |
| Morning start time | Consistent | Shading, orientation |
Automated alerts: Set thresholds for email/SMS notification when KPIs fall outside expected ranges.
- PVOutput - Live PV Data https://pvoutput.org/